Security Levels - Siemens SIMATIC CPU 410 System Manual

Process control system, process automation/cpu
Table of Contents

Advertisement

Special functions of the CPU 410

9.2 Security levels

9.2
Security levels
You can define a protection level for your project in order to prevent unauthorized access to
the CPU programs. The objective of these protection level settings is to grant a user access
to specific programming device functions which are not protected by password, and to allow
that user to execute those functions on the CPU.
Setting protection levels
You can set the CPU protection levels 1 to 3 in HW Config.
The following table shows the protection levels of a CPU.
Table 9- 1
Protection levels of a CPU
CPU function
Display of list of blocks
Monitor variables
Module status STACKS
Operator control and monitoring func-
tions
S7 communication
Read time of day
Set time of day
Block status
Load in PG
Controlling selection
Modify variable
Breakpoint
Clear breakpoint
Stop a CPU or the system
Load in CPU
Delete blocks
Compress memory
Memory reset
Firmware update
A password is required if the program has a safety program.
*
Note
Any set up access right is not canceled until you stop the SIMATIC Manager. You should
reset the access right once again to prevent unauthorized access. You reset the access right
in the SIMATIC Manager with the menu command PLC > Access Rights > Cancel.
134
Protection level 1
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
*
Access granted
*
Access granted
*
Access granted
*
Access granted
*
Access granted
*
Protection level 2
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
Protection level 3
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Access granted
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required
Password required