Siemens SIMATIC CPU 410 System Manual page 258

Process control system, process automation/cpu
Table of Contents

Advertisement

Technical data
16.1 Technical specifications of CPU 410-5H; (6ES7410-5HX08-0AB0)
Article number
Autocrossing
System redundancy
Redundant subnetworks
Change of IP address at runtime, supported
Number of connection resources
Interface types
Number of ports
integrated switch
Media redundancy
supported
Switchover time on line break, typ.
Number of stations in the ring, max.
Functionality
PROFINET IO Controller
PROFINET IO Device
PROFINET CBA
Open IE communication
Web server
PROFINET IO Controller
Transmission rate, max.
Services
PG/OP communication
S7 routing
S7 communication
Open IE communication
Shared device
Prioritized startup
Number of connectable IO Devices,
max.
Number of connectable IO Devices for
RT, max.
of which in line, max.
Activation/deactivation of IO Devices
IO Devices changing during operation
(partner ports), supported
Device replacement without swap me-
dium
Send cycles
258
6ES7410-5HX08-0AB0
Yes
Yes
Yes
No
120
2
Yes
Yes
< 200 ms
50
Yes
No
No
Yes
No
100 Mbit/s
Yes
Yes
Yes
Yes
No; however, usable as part of S7
No
250
250
250
Yes; Single mode only
No
Yes
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 410 smartSimatic pcs 7