Replacement of failed components during redundant operation
13.1 Replacement of central components
Starting situation
Failure
Simultaneous failure of both fiber-optic cables
The S7-400H is in the redundant system state
and both fiber-optic cables fail.
Procedure
The described double fault results in loss of redundancy and partial or complete failure of
switched DP or PN I/O. In this event proceed as follows:
Step
1
2
3
4
230
What to do?
Switch off one subsystem.
Replace the faulty components.
Turn the subsystem back on.
Start the CPU.
How does the system react?
Both CPUs report the event in the diagnostic
buffer and via OB 72.
Both CPUs become master CPU and remain
in RUN.
The LEDs IFM1F and IFM2F are lit on both
CPUs.
How does the system react?
-
-
LEDs IFM1F and IFMF2F go off. The
LED MSTR of the switched on subsys-
tem goes out.
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU switches to RUN (redundant
system state) and operates as standby
CPU.