5. Electrical installation
Unsuccessful AMA
1.
2.
5
Set up the desired limits for speed and ramp
time.
Minimum Reference
Maximum Reference
42
The frequency converter enters into alarm mode. A description of the alarm can be found
Troubleshooting
in the
section.
"Report Value" in the [Alarm Log] shows the last measuring sequence carried out by the
AMA, before the frequency converter entered alarm mode. This number along with the
description of the alarm will assist troubleshooting. If contacting Danfoss Service, make
sure to mention number and alarm description.
NB!
Unsuccessful AMA is often caused by incorrectly entered motor name plate data or
too big difference between the motor power size and the frequency converter power
size.
par. 3-02
par. 3-03
MG.20.M2.02 - VLT
Step 4. Set speed limit and ramp time
Motor Speed Low Limit par. 4-11 or 4-12
Motor Speed High Lim-
it
Ramp 1 Ramp Up Time
[s]
Ramp 1 Ramp Down
Time 1 [s]
®
is a registered Danfoss trademark
®
VLT
AQUA Drive
Operating Instructions
par. 4-13 or 4-14
par. 3-41
par. 3-42