VLT
AQUA Drive
Operating Instructions
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Analog output:
Number of programmable analog outputs
Terminal number
Current range at analog output
Max. load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Control card, 24 V DC output:
Terminal number
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same
potential as the analog and digital inputs and outputs.
Relay outputs:
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Relay 02 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation
(PELV).
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
1)
(Inductive load @ cosφ 0.4)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
(Inductive load)
1)
on 4-5 (NO) (Resistive load)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
on 4-5 (NO) (Resistive load)
1)
on 4-5 (NO) (Inductive load)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load)
®
MG.20.M2.02 - VLT
is a registered Danfoss trademark
Max. error: 0.8 % of full scale
1-3 (break), 1-2 (make)
240 V AC, 0.2 A
4-6 (break), 4-5 (make)
240 V AC, 0.2 A
240 V AC, 0.2A
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
9. Specifications
: 200 Hz
1
42
0/4 - 20 mA
500 Ω
8 bit
9
12, 13
: 200 mA
2
240 V AC, 2 A
60 V DC, 1A
24 V DC, 0.1A
240 V AC, 2 A
80 V DC, 2 A
24 V DC, 0.1A
240 V AC, 2 A
50 V DC, 2 A
24 V DC, 0.1 A