9. Specifications
Normal overload 110% for 1 minute
Mains supply 200 - 240 VAC
Frequency converter
Typical Shaft Output [kW]
Typical Shaft Output [HP] at 208 V
Encapsulation
IP 20
IP 55
IP 66
Output current
Max. input current
9
1.
2.
3.
4.
124
Continuous
(3 x 200-240 V ) [A]
Intermittent
(3 x 200-240 V ) [A]
Continuous
kVA (208 V AC) [kVA]
Max. cable size:
(mains, motor, brake)
[mm
2
/AWG]
Continuous
(3 x 200-240 V ) [A]
Intermittent
(3 x 200-240 V ) [A]
Max. pre-fuses
Environment
Estimated power loss
at rated max. load [W]
Weight enclosure IP20 [kg]
Weight enclosure IP21 [kg]
Weight enclosure IP55 [kg]
Weight enclosure IP 66 [kg]
Efficiency
4)
For type of fuse see section
American Wire Gauge
Measured using 5 m screened motor cables at rated load and rated frequency
The typical power loss is at normal load conditions and expected to be within +/- 15%
(tolerance relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency
motors will also add to the power loss in the frequency converter and vice versa.
If the switching frequency is raised from nominal the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and cus-
tomer load may add up to 30W to the losses. (Though typically only 4W extra for a fully
loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement
inaccuracy must be allowed for (+/- 5%).
MG.20.M2.02 - VLT
P1K1
P1K5
1.1
1.5
1.5
A2
A2
A5
A5
A5
A5
6.6
7.5
7.3
8.3
2.38
2.70
5.9
6.8
6.5
7.5
1)
20
20
[A]
63
82
4)
4.9
4.9
5.5
5.5
13.5
13.5
13.5
13.5
0.96
0.96
Fuses
®
is a registered Danfoss trademark
VLT
Operating Instructions
P2K2
P3K0
P3K7
2.2
3
3.7
2
3
4
5
A2
A3
A3
A5
A5
A5
A5
A5
A5
10.6
12.5
16.7
11.7
13.8
18.4
3.82
4.50
6.00
4/10
9.5
11.3
15.0
10.5
12.4
16.5
20
32
32
116
155
185
4.9
6.6
6.6
5.5
7.5
7.5
13.5
13.5
13.5
13.5
13.5
13.5
0.96
0.96
0.96
®
AQUA Drive