Wizard - Quick Start (Volume - Linearization)

Step 1 – Identification
1)
Navigate to Configure/Setup > Wizard > Wizard - Quick Start (Volume -
Linearization).
2)
You can accept the default values without modification. (TAG, Long TAG, Descriptor,
Message, and Date fields can be left blank.) If desired, make changes then click on
Next.
Step 2 – Application
1.
Select the Siemens transducer connected to the device.
2.
The Application Type defaults to Volume.
3.
Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
4.
Click on Next.
1.
For details see parameter
Instructions (7ML19985MV01).
Page 60
COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL
1
2. 1 .3.Sensor Mode
in SITRANS LUT400 (HART) Operating
A5E33701270