Constant For Quick Setback And Optimum Start Control (Kon); Quick Setback Without Room Influence; Optimum Start Control Without Influence - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Important
Setting
Effect
Example
Note
144/184
Siemens Building Technologies
Landis & Staefa Division
3.13
Constant for quick setback and optimum
start control (KON)
Making use of the building's thermal storage capacity.
Quick setback is dependent on whether or not a room temperature sensor is used.
Therefore, we speak of quick setback with or without room influence.
This setting is active only if no room sensor is used.
Setting range
0...20
The duration of quick setback and the forward shift will be changed.
Entry:
Increase:
Longer setback and forward shift times.
For heavy and well insulated buildings that cool down slowly and that
require longer heating up times.
Decrease:
Shorter setback and forward shift times.
For light and poorly insulated buildings that cool down quickly and that
require shorter heating up times.
3.13.1

Quick setback without room influence

Quick setback is started as soon as a change to a lower room temperature setpoint
takes place (e.g. switching times in automatic mode).
The heating circuit pump will be deactivated until the quick setback time has elapsed,
which is generated from setting 32
room temperature setpoint change.
The example applies to a setpoint step change of 4°C (e.g. TRw from 20 to 16 °C):
TAgem
0
- 20
0
- 10
0
0
0
+10
0
If a room sensor is connected, the quick setback time will not be generated from this
setting. Also refer to "quick setback with room temperature influence" in Index.
3.13.2

Optimum start control without influence

Also refer to "optimum start control" in Index.
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
, the composite outside temperature and the
OEM
Setting on line 32
4
8
0
0
0,5
1
3
6
5
11
Values in hours
Factory setting
2
OEM
12
15
0
0
1.5
2
9
11
15 (16,5)
15 (21)
20
0
2.5
15
15 (27)
CE1P2374E