Quick Guide
1
1
CAUTION
If reinserted, only use M3x12 screw.

1.2.4 Avoid Unintended Start

While the frequency converter is connected to mains, the
motor can be started/stopped using digital commands, bus
commands, references or via the LCP or LOP.
Disconnect the frequency converter from mains
whenever personal safety considerations make it
necessary to avoid unintended start of any
motors.
To avoid unintended start, always press [Off/
Reset] before changing parameters.

1.2.5 Disposal Instruction

1.3.2 Side-by-Side Installation

The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
Frame
IP class
H1
H2
H3
H4
H5
H6
H7
H8
H9
H10
Table 1.5 Clearance
NOTICE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.
4
Equipment containing electrical components
must not be disposed of together with domestic
waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
3x200-240 V
IP20
0.25-1.5
IP20
2.2
IP20
3.7
IP20
5.5-7.5
IP20
11
IP20
15-18.5
IP20
22-30
IP20
37-45
IP20
IP20
®
VLT
HVAC Basic Drive FC 101 Quick Guide

1.3 Installation

1.3.1 Before Starting Repair Work

1.
2.
3.
Power [kW]
3x380-480 V
0.37-1.5
2.2-4
5.5-7.5
11-15
18.5-22
30-45
55-75
90
MG18A502 - Rev. 2013-08-09
Disconnect from mains (and external DC supply, if
present).
Wait as stated in Table 1.1 for discharge of the
DC-link.
Remove motor cable.
Clearance above/below [mm/inch]
3x525-600 V
18.5-30
37-55
75-90
2.2-7.5
11-15
100/4
100/4
100/4
100/4
100/4
200/7.9
200/7.9
225/8.9
100/4
200/7.9