1.7.5 General Specifications
Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips in case of overtemperature
The frequency converter is protected against short-circuits between motor terminals U, V, W.
When a motor phase is missing, the frequency converter trips and issues an alarm.
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips, when the intermediate
circuit voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5, I2, I3, I4
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8, I6-I8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Cable lengths and cross sections
Max. motor cable length, screened/armoured (EMC correct installation)
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mains*
Cross section DC terminals for filter feedback on enclosure frame H1-H3, I2, I3, I4
Cross section DC terminals for filter feedback on enclosure frame H4-H5
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Minimum cross section to control terminals
*See 1.7.2 Mains Supply 3x380-480 V AC for more information
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic '0' PNP
Voltage level, logic '1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
42
VLT
i
®
HVAC Basic Drive FC 101 Quick Guide
MG18A502 - Rev. 2013-08-09
200-240 V ±10%
380-480 V ±10%
525-600 V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
Max. 2 times/min.
Max. 1 time/min.
overvoltage category III/pollution degree 2
0-100% of supply voltage
plus
0-200 Hz (VVC
), 0-400 Hz (u/f)
See 1.7.4 EMC Test Results
4 mm
16 mm
2.5 mm
2.5 mm
0.05 mm
50/60 Hz
(>0.98)
Unlimited
0.05-3600 s
50 m
2
/11 AWG
2
/6 AWG
2
/14 AWG)
2
/14 AWG)
2
/30 AWG
4
18, 19, 27, 29
PNP or NPN
0-24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
Approx. 4 kΩ