Quick Guide
1
1
Fault
Alarm/
number
Warning
Number
52
53
54
55
56
57
58
59
60
66
69
79
80
87
95
126
200
202
250
251
Table 1.25 Warnings and Alarms
34
Fault text
Warning Alarm
Bit
AMA low Inom
AMA big motor
AMA small mot
AMA par. range
AMA user
interrupt
AMA timeout
AMA internal
25
Current limit
44
External Interlock
Heat sink
26
Temperature Low
1
Pwr. Card Temp
Illegal power
section configu-
ration
29
Drive initialised
47
Auto DC Braking
40
Broken Belt
Motor Rotating
Fire Mode
Fire Mode Limits
Exceeded
New sparepart
New Typecode
®
VLT
HVAC Basic Drive FC 101 Quick Guide
Trip
Cause of problem
locked
X
The motor current is too low. Check the settings.
X
The motor is too big to perform AMA.
X
The motor is too small to perform AMA.
The parameter values found from the motor are outside
X
acceptable range
X
The AMA has been interrupted by the user
Try to start the AMA again a number of times, until the AMA
is carried out.
NOTICE
Repeated runs may heat the motor to a level where
X
the resistance Rs and Rr are increased. In most cases,
however, this is not critical
X
X
Contact the local Danfoss supplier.
X
The current is higher than the value in 4-18 Current Limit
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
X
external interlock and reset the frequency converter (via
serial communication, digital I/O, or by pressing reset button
on keypad).
This warning is based on the temperature sensor in the IGBT
X
module (Only on 400 V 30-90 kW units).
The temperature sensor on the power card is either too hot
X
X
X
or too cold.
X
X
Internal fault. Contact the local Danfoss supplier.
X
All parameter settings are initialized to default settings.
X
The drive is auto DC braking
Torque is below the torque level set for no load, indicating a
X
X
broken belt. See parameter group 22-6* Broken Belt Detection.
X
High back-emf voltage. Stop the rotor of the PM motor.
X
Fire mode has been activated
Fire Mode has suppressed one or more warranty voiding
X
alarms
The power or switch mode power supply has been
X
X
exchanged. (Only on 400 V 30-90 kW units). Contact the local
Danfoss supplier
The frequency converter has a new type code (Only on 400 V
X
X
30-90 kW units). Contact the local Danfoss supplier.
MG18A502 - Rev. 2013-08-09