Quick Guide
Motor set-up
The Quick Menu Motor Set-up guides through the needed
motor parameters.
Parameter
Range
0-03 Regional
[0] Interna-
Settings
tional
[1] US
0-06 GridType [0] -[132] see
start -up
wizard for
open loop
application
1-10 Motor
*[0] Motor
Construction
construction
[1] PM, non
salient SPM
1-20 Motor
0.12-110 kW/
Power
0.16-150 hp
1-22 Motor
50.0-1000.0 V
Voltage
1-23 Motor
20.0-400.0 Hz
Frequency
1-24 Motor
0.01-10000.00
Current
A
1-25 Motor
100.0-9999.0
Nominal
RPM
Speed
1-26 Motor
0.1-1000.0
Cont. Rated
Torque
1-30 Stator
0.000-99.990
Resistance (Rs)
®
VLT
HVAC Basic Drive FC 101 Quick Guide
Default
Function
0
Size selected Select operating
mode for restart
upon
reconnection of
the drive to
mains voltage
after power
down
[0]
Asynchron
Size related
Enter motor
power from
nameplate data
Size related
Enter motor
voltage from
nameplate data
Size related
Enter motor
frequency from
nameplate data
Size related
Enter motor
current from
nameplate data
Size related
Enter motor
nominal speed
from nameplate
data
Size related
This parameter is
available only
when 1-10 Motor
Construction
Design is set to
[1] PM, non-
salient SPM.
NOTICE
Changing this
parameter
affects settings
of other
parameters
Size related
Set the stator
resistance value
MG18A502 - Rev. 2013-08-09
Parameter
Range
1-37 d-axis
0-1000
Inductance
(Ld)
1-39 Motor
2-100
Poles
1-40 Back EMF
10-9000
at 1000 RPM
1-73 Flying
[0] Disabled
Start
[1] Enabled
3-41 Ramp 1
0.05-3600.0 s
Ramp Up
Time
3-42 Ramp 1
0.05-3600.0 s
Ramp Down
Time
4-12 Motor
0.0-400 Hz
Speed Low
Limit [Hz]
4-14 Motor
0.0-400 Hz
Speed High
Limit [Hz]
4-19 Max
0-400
Output
Frequency
Table 1.24 Motor Set-up
Changes Made
Changes Made lists all parameters changed from default
settings.
The list shows only parameters which have been
changed in the current edit-setup.
Parameters which have been reset to default
values are not listed.
The message 'Empty' indicates that no
parameters have been changed.
Default
Function
Size related
Enter the value
of the d-axis
inductance.
Obtain the value
from the
permanent
magnet motor
data sheet. The
de-axis
inductance
cannot be found
by performing an
AMA.
4
Enter the number
of motor poles
Size related
Line-Line RMS
back EMF voltage
at 1000 RPM
0
Select Enable to
enable the
frequency
converter to
catch a spinning
motor
Size related
Ramp up time
from 0 to rated
1-23 Motor
Frequency
Size related
Ramp down time
from rated
1-23 Motor
Frequency to 0
0.0 Hz
Enter the
minimum limit
for low speed
65
Enter the
maximum limit
for high speed
Size related
Enter the
maximum output
frequency value
29