1.5 Acoustic Noise or Vibration

If the motor or the equipment driven by the motor - e.g. a fan blade - is making noise or vibrations at certain frequencies,
try the following:
Speed Bypass, parameter group 4-6* Speed Bypass
Over-modulation, 14-03 Overmodulation set to [0] Off
Switching pattern and switching frequency parameter group 14-0* Inverter Switching
Resonance Dampening, 1-64 Resonance Dampening

1.6 Warnings and Alarms

Fault
Alarm/
Fault text
number
Warning
Bit
Number
2
16
Live zero error
4
14
Mains ph. loss
7
11
DC over volt
8
10
DC under volt
9
9
Inverter overload
10
8
Motor ETR over
11
7
Motor th over
13
5
Over Current
14
2
Earth Fault
16
12
Short Circuit
17
4
Ctrl. word TO
24
50
Fan Fault
30
19
U phase loss
31
20
V phase loss
32
21
W phase loss
38
17
Internal fault
44
28
Earth Fault
Control Voltage
47
23
Fault
48
25
VDD1 supply low
AMA calibration
50
failed
51
15
AMA Unom,Inom
®
VLT
HVAC Basic Drive FC 101 Quick Guide
Warning Alarm
Trip
Cause of problem
locked
Signal on terminal 53 or 54 is less than 50% of value set in
6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low Current,
X
X
6-20 Terminal 54 Low Voltageor 6-22 Terminal 54 Low
Current. See also parameter group 6-0* Analog I/O Mode
Missing phase on supply side or too high voltage imbalance.
X
X
X
Check supply voltage. See 14-12 Function at Mains Imbalance
X
X
Intermediate circuit voltage exceeds limit.
Intermediate circuit voltage drops below "voltage warning
X
X
low" limit.
X
X
More than 100% load for too long.
Motor is too hot due to more than 100% load for too long.
X
X
See 1-90 Motor Thermal Protection
Thermistor or thermistor connection is disconnected. See
X
X
1-90 Motor Thermal Protection.
X
X
X
Inverter peak current limit is exceeded.
X
X
Discharge from output phases to ground.
X
X
Short-circuit in motor or on motor terminals.
No communication to frequency converter. See parameter
X
X
group 8-0* General Settings
X
X
The fan is not working (Only on 400 V 30-90 kW units).
Motor phase U is missing. Check the phase. See 4-58 Missing
X
X
Motor Phase Function.
Motor phase V is missing. Check the phase. See 4-58 Missing
X
X
Motor Phase Function.
Motor phase W is missing. Check the phase. See 4-58 Missing
X
X
Motor Phase Function.
X
X
Contact the local Danfoss supplier.
Discharge from output phases to ground, using the value of
X
X
15-31 Alarm Log Value if possible.
X
X
X
24 V DC may be overloaded.
X
X
Control voltage low. Contact the local Danfoss supplier
X
Contact the local Danfoss supplier.
The setting of motor voltage, motor current and motor
X
power is presumably wrong. Check the settings.
MG18A502 - Rev. 2013-08-09
1
1