1.3.6 Fuses and Circuit Breakers

Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear,
machines etc., must be short-circuit and overcurrent protected according to national and local regulations.
Short circuit protection
Danfoss recommends using the fuses and circuit breakers listed in Table 1.19 and to protect service personnel or other
equipment in case of an internal failure in the unit or short-circuit on DC-link. The frequency converter provides full short
circuit protection in case of a short-circuit on the motor.
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Circuit breakers and fuses must be designed for protection in a
circuit capable of supplying a maximum of 100,000 A
UL/Non UL compliance
Use the circuit breakers or fuses listed in Table 1.19, to ensure compliance with UL or IEC 61800-5-1.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10,000 Arms (symmetrical),
480 V maximum.
In the event of malfunction, failure to follow the protection recommendation may result in damage to the frequency
converter.
UL
Power [kW]
3x200-240 V IP20
0.25
0.37
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Cutler-Hammer
18.5
EGE3100FFG
22
Cutler-Hammer
JGE3150FFG
30
37
Cutler-Hammer
45
JGE3200FFG
3x380-480 V IP20
0.37
0.75
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
®
VLT
HVAC Basic Drive FC 101 Quick Guide
(symmetrical), 480 V maximum.
rms
Circuit Breaker
Non UL
Bussmann
Type RK5
Moeller NZMB1-
A125
Moeller NZMB1-
A160
Moeller NZMB1-
A200
MG18A502 - Rev. 2013-08-09
Fuse
UL
Bussmann
Bussmann
Type RK1
Type J
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-15
KTN-R15
JKS-15
FRS-R-25
KTN-R25
JKS-25
FRS-R-50
KTN-R50
JKS-50
FRS-R-50
KTN-R50
JKS-50
FRS-R-80
KTN-R80
JKS-80
FRS-R-100
KTN-R100
JKS-100
FRS-R-100
KTN-R100
JKS-100
FRS-R-150
KTN-R150
JKS-150
FRS-R-150
KTN-R150
JKS-150
FRS-R-200
KTN-R200
JKS-200
FRS-R-200
KTN-R200
JKS-200
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-25
KTS-R25
JKS-25
FRS-R-25
KTS-R25
JKS-25
FRS-R-50
KTS-R50
JKS-50
FRS-R-50
KTS-R50
JKS-50
FRS-R-80
KTS-R80
JKS-80
FRS-R-80
KTS-R80
JKS-80
Non UL
Bussmann
Max fuse
Type T
Type G
JJN-10
10
JJN-10
10
JJN-10
10
JJN-10
10
JJN-15
16
JJN-25
25
JJN-50
50
JJN-50
50
JJN-80
65
JJN-100
125
JJN-100
125
JJN-150
160
JJN-150
160
JJN-200
200
JJN-200
200
JJS-10
10
JJS-10
10
JJS-10
10
JJS-15
16
JJS-15
16
JJS-15
16
JJS-25
25
JJS-25
25
JJS-50
50
JJS-50
50
JJS-80
65
JJS-80
65
15