Danfoss VLT HVAC Basic Drive FC 101 Quick Manual page 46

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Quick Guide
1
1
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
A)
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure
Enclosure kit available
Vibration test
Max. relative humidity
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Derating for high ambient temperature, see .
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance, enclosure frame H1-H5
Minimum ambient temperature at reduced performance, enclosure frame H6-H10
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see
Safety standards
EMC standards, Emission
EMC standards, Immunity
44
®
VLT
HVAC Basic Drive FC 101 Quick Guide
A)
5%-95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
See max. output current at 40/50 °C in 1.7.2 Mains Supply 3x380-480 V AC
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
MG18A502 - Rev. 2013-08-09
EN/IEC 61800-5-1, UL 508C
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
61000-4-5, EN 61000-4-6
50
10.5 V ±0.5 V
25 mA
IP20
IP21, TYPE 1
1.0 g
Class 3C3
Class 3C2
Class 3C3
0 °C
-20 °C
-10 °C
-30 to +65/70 °C
1000 m
3000 m

Advertisement

Table of Contents
loading