Danfoss VLT HVAC Basic Drive FC 101 Quick Manual page 26

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Quick Guide
1
1
Parameter
1-24 Motor Current
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-29 Automatic Motor Adaption
(AMA)
1-30 Stator Resistance (Rs)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-73 Flying Start
1-73 Flying Start
3-02 Minimum Reference
3-03 Maximum Reference
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time
4-12 Motor Speed Low Limit [Hz]
4-14 Motor Speed High Limit [Hz]
4-19 Max Output Frequency
5-40 Function Relay [0] Function
relay
5-40 Function Relay [1] Function
relay
6-10 Terminal 53 Low Voltage
6-11 Terminal 53 High Voltage
6-12 Terminal 53 Low Current
6-13 Terminal 53 High Current
24
®
VLT
HVAC Basic Drive FC 101 Quick Guide
Option
0.01-10000.00 A
100.0-9999.0 RPM
0.1-1000.0
See 1-29 Automatic Motor
Adaption (AMA)
0.000-99.990
0-1000
2-100
10-9000
[0] Disabled
[1] Enabled
-4999-4999
-4999-4999
0.05-3600.0 s
0.05-3600.0 s
0.0-400 Hz
0.0-400 Hz
0-400
See 5-40 Function Relay
See 5-40 Function Relay
0-10 V
0-10 V
0-20 mA
0-20 mA
MG18A502 - Rev. 2013-08-09
Default
Function
Size related
Enter motor current from nameplate data
Size related
Enter motor nominal speed from nameplate
data
Size related
This parameter is available only when
1-10 Motor Construction Design is set to [1]
PM, non-salient SPM.
NOTICE
Changing this parameter will affect
settings of other parameters
Off
Performing an AMA optimizes motor
performance
Size related
Set the stator resistance value
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
4
Enter the number of motor poles
Size related
Line-Line RMS back EMF voltage at 1000 RPM
When PM is selected, Flying Start is enabled
and can not disable
0
Select [1] Enable to enable the drive to catch
a motor spinning due to mains drop-out.
Select [0] Disable if this function is not
required. When is enabled 1-71 Start Delay
and 1-72 Start Function have no function. is
active in VVC
0
The minimum reference is the lowest value
obtainable by summing all references
50
The maximum reference is the lowest
obtainable by summing all references
Size related
Ramp up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected;
ramp up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected
Size related
Ramp down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected
0 Hz
Enter the minimum limit for low speed
65 Hz
Enter the maximum limit for high speed
Size related
Enter the maximum output frequency value
Alarm
Select the function to control output relay 1
Drive running
Select the function to control output relay 2
0.07 V
Enter the voltage that corresponds to the low
reference value
10 V
Enter the voltage that corresponds to the
high reference value
4
Enter the current that corresponds to the low
reference value
20
Enter the current that corresponds to the high
reference value
plus
mode only