Quick Guide
The Start-up Wizard for Open Loop Applications
Parameter
0-03 Regional Settings
0-06 GridType
1-10 Motor Construction
1-20 Motor Power
1-22 Motor Voltage
1-23 Motor Frequency
®
VLT
HVAC Basic Drive FC 101 Quick Guide
Option
[0] International
[1] US
[0] 200-240 V/50 Hz/IT-grid
[1] 200-240 V/50 Hz/Delta
[2] 200-240 V/50 Hz
[10] 380-440 V/50 Hz/IT-grid
[11] 380-440 V/50 Hz/Delta
[12] 380-440 V/50 Hz
[20] 440-480 V/50 Hz/IT-grid
[21] 440-480 V/50 Hz/Delta
[22] 440-480 V/50 Hz
[30] 525-600 V/50 Hz/IT-grid
[31] 525-600 V/50 Hz/Delta
[32] 525-600 V/50 Hz
[100] 200-240 V/60 Hz/IT-grid
[101] 200-240 V/60 Hz/Delta
[102] 200-240 V/60 Hz
[110] 380-440 V/60 Hz/IT-grid
[111] 380-440 V/60 Hz/Delta
[112] 380-440 V/60 Hz
[120] 440-480 V/60 Hz/IT-grid
[121] 440-480 V/60 Hz/Delta
[122] 440-480 V/60 Hz
[130] 525-600 V/60 Hz/IT-grid
[131] 525-600 V/60 Hz/Delta
[132] 525-600 V/60 Hz
*[0] Asynchron
[1] PM, non salient SPM
0.12-110 kW/0.16-150 hp
50.0-1000.0 V
20.0-400.0 Hz
MG18A502 - Rev. 2013-08-09
Default
Function
0
Size related
Select operating mode for restart upon
reconnection of the drive to mains voltage
after power down
[0] Asynchron
Setting the parameter value might change
these parameters:
1-01 Motor Control Principle
1-03 Torque Characteristics
1-14 Damping Gain
1-15 Low Speed Filter Time Const.
1-16 High Speed Filter Time Const.
1-17 Voltage filter time const.
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-66 Min. Current at Low Speed
1-72 Start Function
1-73 Flying Start
4-19 Max Output Frequency
4-58 Missing Motor Phase Function
Size related
Enter motor power from nameplate data
Size related
Enter motor voltage from nameplate data
Size related
Enter motor frequency from nameplate data
1
1
23