Frequency converter
Typical shaft output [kW]
Typical shaft output [hp]
IP20 frame
Max. cable size in terminals
2
(mains, motor) [mm
/AWG]
Output current - 40 °C ambient temperature
Continuous (3x380-440 V)[A]
Intermittent (3x380-440 V) [A]
Continuous (3x440-480 V) [A]
Intermittent (3x440-480 V) [A]
Max. input current
Continuous (3x380-440 V) [A]
Intermittent (3x380-440 V) [A]
Continuous (3x440-480 V) [A]
Intermittent (3x440-480 V) [A]
Max. mains fuses
Estimated power loss [W],
1)
best case/typical
Weight enclosure IP20 [kg]
Efficiency [%], best case/typical 1
Output current - 50 °C ambient temperature
Continuous (3x380-440 V) [A]
Intermittent (3x380-440 V) [A]
Continuous (3x440-480 V) [A]
Intermittent (3x440-480 V) [A]
Table 1.28 3x380-480 V AC, P18K-P90K, H5-H8
®
VLT
HVAC Basic Drive FC 101 Quick Guide
P18K
P22K
P30K
18.5
22.0
30.0
25.0
30.0
40.0
H5
H5
H6
16/6
16/6
35/2
37.0
42.5
61.0
40.7
46.8
67.1
34.0
40.0
52.0
37.4
44.0
57.2
35.2
41.5
57.0
38.7
45.7
62.7
29.3
34.6
49.2
32.2
38.1
54.1
412/456
475/523
733
9.5
9.5
24.5
98.1/97.9
98.1/97.9
97.8
34.1
38.0
48.8
37.5
41.8
53.7
31.3
35.0
41.6
34.4
38.5
45.8
MG18A502 - Rev. 2013-08-09
P37K
P45K
P55K
37.0
45.0
55.0
50.0
60.0
70.0
H6
H6
H7
35/2
35/2
50/1
73.0
90.0
106.0
80.3
99.0
116.0
65.0
80.0
105.0
71.5
88.0
115.0
70.0
84.0
103.0
77.0
92.4
113.0
60.6
72.5
88.6
66.7
79.8
97.5
922
1067
1133
24.5
24.5
36.0
97.7
98
98.2
58.4
72.0
74.2
64.2
79.2
81.6
52.0
64.0
73.5
57.2
70.4
80.9
1
P75K
P90K
75.0
90.0
100.0
125.0
H7
H8
95/0
120/250MC
M
147.0
177.0
161.0
194.0
130.0
160.0
143.0
176.0
140.0
166.0
154.0
182.0
120.9
142.7
132.9
157.0
1733
2141
36.0
51.0
97.8
97.9
102.9
123.9
113.2
136.3
91.0
112.0
100.1
123.2
37
1