1.1.24. This UPS has been designed and constructed to protect your assets from
the wide range of power aberrations experienced on Utility power lines
today. It is your insurance for reliable, clean and stable voltage supply. It is
worth taking care to install the system correctly and to have it maintained
correctly by your local dealer.
1.1.25. SAVE THESE INSTRUCTIONS - This Manual Contains Important
Instructions that should be followed during Installation and Maintenance of
the UPS and Batteries.
1.1.26. Intended for Installation in a Controlled Environment.
1.1.27. Disconnection Device-CAUTION - A disconnect switch shall be provided by
others for AC output circuit. To reduce the risk of fire, connect only to a
circuit provided with branch circuit over-current protection for 30 amperes
for 6Kva, for 50 amperes for 10Kva rating in accordance with the National
Electric Code, ANSI/NFPA 70.
1.1.28. CAUTION - To reduce the risk of fire, unit input connect only to a circuit
provided with branch circuit over-current protection for 40 amperes for
6Kva and 10Kva amperes rating in accordance with the National Electric
Code, ANSI/NFPA 70.
1.1.29. Maximum ambient operating temperature is up to 40C.
1.2.

Storage Instruction

For extended storage through moderate climate, the batteries should be
charged for 12 hours every 3 months by plugging the UPS power cord into the
wall receptacle and turn on input breaker on front panel. Repeat this procedure
every 2 months under high temperature environment.