Ablerex ODIN User Manual page 28

Parallel redundancy on-line ups 6k/10kva
Table of Contents

Advertisement

3.5.4.4.
3.5.5.
UPS Default Settings and their alternatives
Make sure the UPS is not "On" yet. Press On Switch
3.5.5.1.
down
will sound twice, the LCD display screen shows as drawing Q1, then the
UPS is under setting mode now.
3.5.5.2.
To scroll down the LCD screen, you may refer to Chapter 3.5.4.2
3.5.5.3.
Except Buzzer (as drawing Q1 & Q2) and Self-test(as drawings R1 &
R2), all the rest default settings may be changed by pressing scroll up
key pad.
3.5.5.4.
Drawings S1 and S2 mean the bypass input acceptable window, it can
be 184Vac~260Vac or 195Vac~260Vac.
3.5.5.5.
Drawing T means the bypass frequency window of the Inverter Output,
the acceptable setting values are ±3Hz and ±1Hz.
3.5.5.6.
Drawing U means the acceptable Inverter Output Voltage, of which
voltage is 200Vac, 208Vac, 220Vac, 230Vac, or 240Vac.
3.5.5.7.
Drawing V1, V2, V3 and V4 mean the operation modes of the UPS, of
which alternative is Online, Eco(Economic) mode, fixed 50Hz Output or
fixed 60Hz Output.
3.5.5.8.
Drawing W means the adjustments of the Inverter Output, which may be
calibrated as 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
3.5.5.9.
Drawing X means a specified address & position of the UPS when the
UPS is in Parallel mode. The settable numbers are from 1st to 4th. The
number must be 1st if the UPS is not in parallel.
3.5.5.10. Drawing Y means the parallel function status. The "P 01" means parallel
function disabled and the "P 02" means parallel function enabled.
3.5.5.11. When all the setting changes are done, you have to press enter
Pad to save all the changes when the LCD screen shows as drawing Z,
then, the LCD screen will show as drawing AA to complete the setting
changes. If you don't want to change those settings, you may press
"OFF"
Drawing AA directly, which means your setting changes are invalid.
Z
key pads simultaneously for approx. 3 seconds, the buzzer
key pads for 5 seconds, then the LCD screen turns to
* Please press Enter key to save data.