Ablerex ODIN User Manual page 18

Parallel redundancy on-line ups 6k/10kva
Table of Contents

Advertisement

Use Mounting Cable Tie to fix cables.
EVOLPACK 6KVA
EVOLPACK10KVA
6. Please refer to the specs of input current, output current and recommended
conductors listed as below:
a. AC input and output (75C minimum copper wire)
Model
6KVA
10KVA
b. Battery input
Model
6KVA
10KVA
Maximum Current
33A
54.3A
Maximum Current
25A
41A
Conductor
Section
AWG #9
AWG #6
Conductor
Section
AWG #10
AWG #10
17
Torque force
23 lb-in