Important Safety Instruction; An Important Notice; Storage Instruction - Ablerex MSRT-Pro 1KVA User Manual

Intelligent true on-line ups for corporate & it user
Hide thumbs Also See for MSRT-Pro 1KVA:
Table of Contents

Advertisement

1.

Important Safety Instruction

1.1. An Important Notice

SAVE THESE INSTRUCTIONS - This Manual Contains Important
Instructions that should be followed during Installation and
Maintenance of the UPS
1.
Do not open the case, as there are no serviceable parts inside. Your
Warranty will be void.
2.
Do not try to repair the unit yourself; contact your local supplier or your
warranty will be void.
3.
If liquids are split onto the UPS or foreign objects dropped into the unit, the
warranty will be null and void.
4.
Do not install the UPS in an environment with sparks, smoke or gas.
5.
This UPS is equipped with an EMI filter. To prevent potential leakage current
hazard, ensure that the AC main supply is securely grounded.
6.
This UPS is designed to be installed and commissioned in a sheltered,
controlled environment as follows:
- Operating temperature 0-40°C and 30-90% non-condensing humidity.
- Always avoid contact with direct sunlight.
- Installing the UPS in inflammable or hazardous environment.
- Dusty, corrosive and salty environments can do damage to any UPS.
- Install the UPS indoors as it is not designed for installation outdoors.
7.
To prevent any overheating of the UPS, keep all ventilation openings free
from obstruction, and do not place anything on top of the UPS. Keep the UPS
rear panel 20 cm away from the wall or other obstructions.
8.
The battery will discharge naturally if the system is unused for any length of
time.
9.
Install the UPS away from objects that give off excessive heat and areas that
are excessively wet.
10. Always switch off the UPS and disconnect the batteries when relocating the
UPS.
11. It should be recharged every 2-3 months if unused. If this is not done, then
the warranty will be null and void. When installed and being used, the
batteries will be automatically recharged and kept in top condition.
12 Make sure that the AC Utility outlet is correctly grounded.
13. Please ensure that the input voltage of the UPS matches the utility supply
voltage. Use a certified input power cable with the correct plugs and sockets
for the appropriate voltage system.
14. Intended for installation in a temperature-controlled, indoor area free of
conductive contaminants.
15. Maximum ambient temperature 40°C
2

1.2. Storage Instruction

For extended storage in moderate climate, the batteries should be charged
for 12 hours every 3 months interval by connecting the UPS to the utility supply
and switch on input breaker located at UPS rear panel. Repeat this procedure
every 2 months if the storage ambient temperature is above 30°C.