Ablerex ODIN User Manual page 20

Parallel redundancy on-line ups 6k/10kva
Table of Contents

Advertisement

3.5.1.5.
Then, the UPS is on Bypass Mode now and it will proceed self-test
automatically. If there is no abnormal message occurred, it means the
pre-startup of the UPS is successful and the charger starts to charge the
batteries.
3.5.1.6.
Press the UPS On Switch
sounds twice and the LCD display changes from drawing B to drawing
C.
C
3.5.1.7.
Then, the UPS is under self-test mode again, the LCD display will
illustrate from drawing C to drawing D and remain approx. 4 seconds
under battery mode, then illustrate from drawing E1 to drawing F if the
self-test is successful.
D
E1
E2
* It shows "test".
* It shows "OK" in self-test
* It shows "Fail" in self-test
for approx. 3 seconds, then the Buzzer
19