3.5.5.12. Turn Off the breaker of Utility Input.
3.5.5.13. Your Setting changes are complete.
3.5.6.
UPS Is Off Due to Unknown Reason and Its Trouble Shooting
3.5.6.1.
If there is a serious abnormal condition occurred, the UPS will lock it
itself in "OFF" position as shown in drawing AA and a abnormal
message will show on the LCD screen.
3.5.6.2.
After 3 seconds, all messages will be locked except Bypass messages
(LED
is locked, the LED
shown on the LCD screen.
3.5.6.3.
To release the UPS lock, please proceed the followings:
3.5.6.3.1.
Check those error messages recorded.
3.5.6.3.2. Check to see Chapter 2.2 to trouble shoot the problem of the UPS.
Otherwise, consult your local distributor for service.
3.5.6.3.3.
Press Off
3.5.6.3.4. Turn Off the Breaker of Utility Input.
3.5.6.3.5.
The UPS lock problem is solved now, but you shall contact with your
Local distributor to make sure the error message shown is solved.
3.5.7.
Shut Off
3.5.7.1.
Press Off
turned off, then the output load is supplied by Bypass loop and the LCD
screen shows as drawing B.
3.5.7.2.
Turn Off the breakers of Utility and Bypass Input.
3.5.7.3.
The UPS is turned off completely.
3.5.8.
Maintenance Bypass Mode
* It shows the UPS is locked.
& LCD
will be extinguished and the LCD
key pad for 5 seconds and buzzer will sound twice.
key pad for about 5 seconds, the Inverter output will be
). In case the Utility is abnormal after the UPS
28
will be