Temperature Specifications; Relative Humidity Specifications; Maximum Vibration Specifications; Maximum Shock Specifications - Dell EMC DSS 9620 Installation And Service Manual

Table of Contents

Advertisement

Temperature specifications

Table 11. Temperature specifications
Temperature
Storage
Continuous operation (altitudes under 950 m / 3,117 ft)
Fresh air
Maximum temperature gradient (operation and storage)

Relative humidity specifications

Table 12. Relative humidity specifications
Relative humidity
Storage
Operating

Maximum vibration specifications

Table 13. Maximum vibration specifications
Maximum vibration
Operating
Storage

Maximum shock specifications

Table 14. Maximum shock specifications
Maximum shock
Operating
Storage
Specifications
–40°C to 65°C (–40°F to 149°F)
10°C to 35°C (50°F to 95°F), avoiding direct sunlight
For information about fresh air, see Expanded Operating Temperature section.
20°C/h (36°F/h)
Specifications
5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be
non-condensing at all times.
10% to 80% relative humidity with 29°C (84.2°)
Specifications
0.26 Grms at 5 Hz to 350 Hz (all operational orientations)
1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested)
Specifications
24 executed shock pulses 6 G in the positive and negative x, y, z axis up to 11
ms (four pulses on each side of the system)
Six consecutively executed shock pulses of 71 G in the positive and negative
x, y, z axes up to 2 ms (one pulse on each side of the system)
Technical specifications