How To Configure; Ip Settings; Ethernet Link Parameters; Configure The Frequency Converter - Danfoss MCA 123 POWERLINK Operating Instructions Manual

Table of Contents

Advertisement

How to Configure

3 How to Configure

3.1.1 IP Settings

All IP-related parameters are located in parameter group
12-0* IP Settings: The parameters are all set to POWERLINK
3
3
standard values, so no setting is needed. In POWERLINK,
the 12-00 IP Address Assignment is fixed to the selection
"From node ID". The IP address does follow the setting in
12-60 Node ID, so that the IP address is 192.168.100.xxx,
where xxx is the node ID. For 12-02 Subnet Mask, this will
be fixed to 255.255.255.0 and can not be changed.
The POWERLINK option offers two ways of IP address
assignment via parameter or DIP switch.

3.1.2 Ethernet Link Parameters

Parameter group 12-1* Ethernet Link Parameters holds
Ethernet Link information:
12-10 Link Status
12-11 Link Duration
12-12 Auto Negotiation
12-13 Link Speed
12-14 Link Duplex
Each port has unique Ethernet Link Parameters.
12-10 Link Status displays Link or No Link according to the
status of the present port.
12-11 Link Duration displays the duration of the link on the
present port. If the link is broken, the counter is reset.
12-12 Auto Negotiation is a feature that enables two
connected Ethernet devices to choose common
transmission parameters, such as speed and duplex mode.
In POWERLINK this feature is fixed to OFF and can not be
changed.
12-13 Link Speed - displays the link speed for each port. If
no link is present, "None" is displayed. In POWERLINK this
feature is fixed to 100 MBaud and can not be changed.
12-14 Link Duplex - displays the duplex mode for each port.
In POWERLINK, the Link Duplex is fixed to half Duplex, and
cannot be changed.
10
MCA 123 POWERLINK Operating Instructions

3.2 Configure the Frequency Converter

3.2.1 VLT Parameters

Pay particular attention to the following parameters when
configuring the frequency converter with a fieldbus
interface.
NOTE
When 8-01 Control Site is set to [2] Control word only, the
settings in 8-50 Coasting Select to 8-56 Preset Reference
Select are overruled, and all act on Bus-control.

3.3 Configure the POWERLINK Network

All POWERLINK stations that are connected to the same
bus network must have a unique Node ID. The Node ID of
the frequency converter can be selected via:
®
MG92C102 - VLT
is a registered Danfoss trademark
0-40 [Hand on] Key on LCP. If the [Hand on] key
on the frequency converter is activated, control of
the frequency converter via the fieldbus interface
is disabled.
After an initial power up, the frequency converter
automatically detects whether a fieldbus option is
installed in slot A, and sets 8-02 Control Word
Source to [Option A]. Adding, changing, or
removing an option from an already commis-
sioned frequency converter does not change
8-02 Control Word Source. However, it causes a
Trip Mode, and the frequency converter displays
an error.
8-10 Control Word Profile. Choose between the
Danfoss FC Profile and the DS 402 profile. The
change of 8-10 Control Word Profile will first be
active at the next powerup.
8-50 Coasting Select to 8-56 Preset Reference Select.
Selection of how to gate fieldbus control
commands with digital input command of the
control card.
8-03 Control Word Timeout Time to 8-05 End-of-
Timeout Function. The reaction in the event of a
bus time-out is set via these parameters.
Hardware switches (from version 2.00)
12-60 Node ID