Table D-10: Data Record 92 - Read Device Diagnosis - Siemens SIMATIC ET 200pro Quick Manual

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

D.3.6
Data record 81 – read base setting DS 131
The structure and content of data record 81 correspond to those of data record
131. Data record 81 delivers the default values for all the parameters of the DS
131.
D.3.7
Data record 92 – read device diagnosis
Ghosted signaling bits are not supported by ET 200pro motor starters.
ID no. Byte
Signaling bit
Switch / Control:
0
301
0
Ready (Automatic)
1
306
0
Motor CLOCKWISE
2
307
0
Motor COUNTER-CLOCK-
WISE
3
309
0
Switching element overload
4
308
0
Switching element defective
5
310
0
Emergency start active
6
302
0
Group error
7
304
0
General warning
0
318
1
Supply voltage for switching
element missing
1
319
1
Mains voltage lost
2
311
1
Lock-out time active
Table D-10: Data record 92 – read device diagnosis
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
Data formats and data records
1)
F no.
Meaning / Acknowledgment
Device ready to operate via host (e.g. PLC)
Signaling bit is continuously updated
Switching element 1 switched on
Signaling bit is continuously updated
Switching element 2 switched on
Signaling bit is continuously updated
F5,
E.g., power semiconductor too hot and tripping
F24
Signaling bit is deleted when cause of the
trip has been removed and acknowledged
with trip reset
F9
E.g., contactor fused, jammed or power semi-
conductor shorted
Signaling bit can only be deleted by switch-
ing the supply voltage (DC 24 V-NS) off / on
when error cause has been removed
Signaling bit is deleted when emergency start
is deactivated
At least 1 error that generates an F no. is set.
Signaling bit is deleted when cause of the trip
has been removed and acknowledged with
trip reset, autoreset, OFF command
At least 1 warning is present
Signaling bit is continuously updated
F17,
Signaling bit is automatically deleted when
F24
cause of the trip has been removed
F17,
Signaling bit is deleted when the cause of the
F24
trip has been removed and acknowledged with
trip reset (occurs even if input or output side of
the primary voltage is missing; valid for soft
starters
For reversing starter
Signaling bit is continuously updated
D-15