2.6

Configuring (project planning)

1. Start the SIMATIC Manager and set up a new project with a DP master (e.g.
CPU315-2 DP) (see
2. Create the PROFIBUS subnet.
3. From the hardware catalog, insert the ET 200pro at the PROFIBUS.
4. Set the PROFIBUS address 6 for ET 200pro.
5. If this has not been done yet, update your software (see
'Updating software') so that the ET 200pro modules become visible. Drag
the individual ET 200pro modules from the hardware catalog into the config-
uration table (see
6. For a complete display of the parameter set for motor starters, open the
screen for the assembly IM 154-. and at 'Operating parameters' set the DP
alarm mode from 'DPV0' (=default) to 'DPV1'. If this is not possible, the
CPU you are using is not suitable for DPV1.
7.
Parameterize the 'Response to residual current detection' for the motor
starter for this example to "Warning".
Assembly /
Order number
DP identifier
2
3RK1304-0SH00-6AA0
3
3RK1304-5xS40-4AA0
4
6ES7141-4BF00-0AA0
1) x = select the current range according to the load you have connected

Table 2-2: Configuration table in 'HW Config'

The following screen should result.

Figure 2-4: Assemblies in 'HW Config'

SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
Figure
2-4).
Figure
2-4).
I addr.
0.0 - 0.7
1)
1.0 - 1.3
3.0 - 3.7
Your file name
Chapter 4.2
O addr.
Comment
Maintenance isolat-
ing module
0.0 - 0.3
DSe motor starter
Electronics module
8 DI DC 24 V
-