Rules for wiring
Warning
Dangerous electrical voltage! Can lead to electrical shocks and burns. Before
starting work, disconnect the system from the power supply.
9.1.1
Selecting the power cables
The wire cross-section of the power cables must be adapted to the relevant
ambient conditions. The most important factors for the wire cross-section are:
• the set current at the device,
• the type of cable routing,
• the ambient temperature,
• the material type (PVC, rubber).
For PVC power cables, e.g. when routed in the cable duct, depending on the
ambient temperature, the following maximum current-carrying capacity results:
2
mm
1.5
2.5
4.0
On wiring, observe the following rules:
Current-carrying capacity of the plug connection
depending on the connectable wire cross-sections and
ambient temperature

Table 9-1: Rules for wiring

9.1.2
Unused connections
Close off unused connections with sealing caps; this is the only way to ensure
type of protection IP65, order number 3RK1902-0CJ00 (10 units) or 3RK1902-
0CK00 (1 unit).
9-2
30°C
40°C
14 A
12.2 A
19 A
16.5 A
26 A
22.6 A
Rules for flexible cables
T
U
45°C
50°C
11.1 A
9.9 A
15.0 A
13.5 A
20.5 A
18.5 A
T
=
u
55°C
2
1.5 mm
12 A
2
2.5 mm
20 A
2
4.0 mm
30 A
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
55°C
08.5 A
11.6 A
15.9 A
Data
40°C
15 A
25 A
35 A