System diagnosis (see also manual 'ET 200pro decentralized peripheral device')
In ET 200pro devices with diagnostic capability, device-specific diagnoses are
recorded via allocated PROFIBUS error numbers. The error numbers in each
case are sent to the ET 200pro interface module IM 154-.
The system diagnosis indicates whether there is a channel error. It also speci-
fies whether other channel-related information is present.
In the diagnosis data record (see manual "Decentralized peripheral device
ET 200pro"), the channel-related diagnosis starts as of byte 19.
For each channel-related diagnosis, 3 bytes are inserted. The corresponding DP
error number (= error type) is inserted in binary code in the 3rd byte in each
case at the bit positions 0 ... 4.
The stored values are extracted by the starter from the diagnoses recorded in
data record 92. As there are insufficient uniquely defined DP error numbers
available for the starter, various DS92 diagnoses must be shown on one and the
same error number (= multiple assignment; see table).
Channel-specific diagnosis
Individual errors
Reserved
Short circuit
Overload
Overtemperature
Upper limit value exceeded
Lower limit value undershot
Error
Parameterization error
Sensor or load voltage missing
Actuator tripping
External error

Table 4-6: System diagnosis

4-16
DP
DS92
error no.
Byte no.
2
1
2
2
3
3
4
2
3
5
0
2
7
4
3
8
4
4
9
0
1
16
8
2
8
0
17
1
4
24
2
1
4
4
4
6
4
7
4
3
26
3
4
5
5
5
7
5
Supported by ET 200pro motor
starters /
DS92 meaning
Temperature sensor short circuit
Circuit breaker tripped
(maintenance isolating module)
Thermal motor model overload
Switching element overload
I
limit value exceeded
e
I
limit value undershot
e
Switching element defective
Incorrect parameter value
Parameter change illegal in the
ON state
Supply voltage for switching ele-
ment missing
Overload tripping
Asymmetry tripping
I
limit value tripping
e
Residual current tripping
Motor block tripping
Current limitation active
(sDSSte / sDSte and sRSSte /
sRSte)
Input tripping
Input tripping (end position clock-
wise)
Input tripping (end position coun-
terclockwise)
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04