Table 9-2: Mounting And Wiring The Power Plug Connector - Siemens SIMATIC ET 200pro Quick Manual

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

Connecting
9.2.4
Mounting and wiring the power plug connector
Mount and wire the power plug connector according to the following
specifications:
Step
1
2
3
4
5
6
7

Table 9-2: Mounting and wiring the power plug connector

9-8
Route the cable through the cable gland, the matching enclosed seal insert
and the plug case.
The seal insert is available in the following grades:
Permitted outer diameter of the cable
7.0 to 10.5 mm
9.0 to 13.0 mm
11.5 to 15.5 mm
Insulate the cable to a length of 20 mm.
Insulate the wires to a length of 8 mm.
Secure the contact sockets / contact pins to the wires by crimping with a
suitable tool (see
Chapter
Sort the contact sockets / contact pins in the socket insert / pin insert
according to the assignments as shown in
9.2.3. The contact sockets / contact pins should not snap into place yet.
Check the correct assignment. Push the contact sockets / contact pins into
the socket insert / pin insert until the snap into place.
Already mounted contact sockets / contact pins can be removed using a
dismounting tool (see
Chapter
Ensure the coding is in the right position. Pull the cables back and use the
enclosed Philips screws to firmly screw the socket insert / pin insert into
the plug case.
Screw the cable gland down firmly. Make sure that the cable is not twisted
against the plug case.
Procedure
A.2) or solder them.
Chapter 9.2.2
A.2).
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
Seal insert
Green
Red
white
and
Chapter