Table D-11: Structure Of The Command Data Record; Table D-12: Data Record 93 - Write Command - Siemens SIMATIC ET 200pro Quick Manual

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

D.3.8
Data record 93 – write command
Structure of the command data record
Byte
Meaning
Command data record
Header label
0
Coordination
1...3
Reserved
Command
4
Number of commands
5
Command 1
6
Command 2
7
Command 3
8
Command 4
9
Command 5

Table D-11: Structure of the command data record

ID no.
Coding
1-byte commands
0
0
Reserved
703
1
Trip reset
713
2
Emergency start ON
714
3
Emergency start OFF
709
4
Operating mode Auto-
matic
710
5
Manual operating mode
711
- bus
712
- local
701
6
Factory setting
704
7
Delete maximum
pointer
715
8
Program memory
module
702
9
Restart
707
10
Parameterization lock
CPU / Master ON
Table D-12: Data record 93 – write command
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
0x20 write via C1 channel (PLC)
0x30 write via C2 channel (PC)
0x40 write via device interface (PC)
Value range 1...5.
Number of subsequent valid commands
Serial no., see table below
Optional (coding see table below)
Optional (coding see table below)
Optional (coding see table below)
Optional (coding see table below)
Command
No function
Resets and acknowledges error messages
Transition to Automatic operating mode
(control by DP master)
Transition to manual operating mode. The motor
starter switches to 'Manual bus operating mode' or
'Manual operation local operating mode' depend-
ing on the interface across which the command is
received.
Recover factory setting of the parameters from
DS 128
The measured values for preventive diagnosis are
deleted (= 0).
Not supported
Trigger new start (same as after mains power ON),
e.g. after reassignment of the station address.
No parameterization by parameterizing master is
possible, or its parameters are ignored
Data formats and data records
Note
Meaning
D-21

Advertisement

Table of Contents