RM3-400/410/420 Series Installation and Operation Guide

Battery Time Remaining

The SC200 or SC100 obtains characterization data from either periodic battery discharges
(SC100) or every full battery discharge (SC200) (to the specified end voltage).
During a battery discharge, the SC200 or SC100 uses this characterization data to calculate an
estimated time until the battery will reach a specified end voltage.
If a battery disconnect LVD is fitted then the end voltage will usually be the voltage at which the
LVD disconnects the battery.
Battery Time Remaining is designed for a constant power load. The accuracy of the time
remaining calculation will be reduced if the dc power system is connected to a predominantly
resistive (constant current) load.
For details refer to Battery Time Remaining in the SC200 or SC100 System Controller Operation
Handbook (see Related Information on page i).