Replacing The Input/Output Board (Some Models Only) - Eaton RM3-400-0330 Installation And Operation Manual

Table of Contents

Advertisement

RM3-400/410/420 Series Installation and Operation Guide
Step 4 - Download the configuration file
1
2
3
Step 5 - Check the system controller operation
1
2
3
4
5
6
Procedure complete
Return the faulty system controller with a completed Equipment Incident Report on page 77.

Replacing the Input/Output Board (some models only)

This procedure only applies to RM3-410/RM3-420 models with an Input/Output (I/O) board
(see Model Numbers on page 2).
Before you start you will require:
A PC/Laptop with DCTools* connected to the system controller or (SC200 only) a web
browser* connected to the system controller via an IP network.
A replacement input/output board.
An anti-static wrist strap to prevent damage to the static sensitive components on the
input/output board.
54
Connect to the system controller with DCTools/Web. See details on page
System Controller Operation Handbook.
If a copy of the old configuration file, or a master configuration file is available,
then use DCTools to restore (download) it to the new system controller.
See Backup and Restore on page
If you receive an error message about the MIB file version, please contact your
Eaton dc product supplier for advice.
If a copy of the old configuration file, or a master configuration file is not
available, then use the keypad or DCTools/Web to change the configuration
settings to the correct values (provided the system controller is set for the correct
nominal system voltage).
Map the I/O board (SC200 only):
In DCTools/Web go to: RXP.
Copy the I/O board serial number(s) from the RXP Devices table to the I/O
Board to Serial Number Mapping table to map an IOB Number to each I/O board
(overwrite an existing serial number if required).
If multiple SiteSure-3G modules are connected use the I/O board Identify function
to physically identify each module. See details in the System Controller Operation
Handbook.
Check that the system controller has registered all rectifiers.
Check all control processes, alarms and current measurement(s).
Check the power system identification parameters and communications settings.
Change the configuration file as required to ensure that the system controller
operates as intended.
Check the system controller time (SC200 only). See details in the System
Controller Operation Handbook.
*See Communications Options in the System Controller Operation Handbook.
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-62E
34