Step 3 - Fit brackets in alternate position (if required)
Step 4 - Replace top cover
Procedure complete

Task 3 - Mount the RM3-400/410/420 in the Rack

Step 1 - Check clearances
RM3-400/410/420s require the following minimum clearances for access and
adequate air flow:
Front:
Rear:
Above/below:
Step 2 - Mount the RM3-400/410/420
1
Rack-mounting bracket (available for 19-inch
and 23-inch wide racks)
24" (600mm)
4" (100mm)
No restriction
Fit cage nuts in the correct positions to match the screw holes in the RM3-
400/410/420 rack mounting brackets.
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-62E
Alternative bracket positions
June 2010
Installation
17