Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

4.
Configuration and Use Manual
Figure B-5:
Supply voltage and resistance requirements
1000
900
800
700
600
500
400
300
200
100
0
12
14
Note
To connect over a HART multidrop network:
a. Attach the leads from the signal converter to any point on the network.
b. Add resistance as necessary to achieve at least one volt across the connection
points.
Important
HART/Bell 202 connections require a voltage drop of 1 VDC. To achieve this, add
resistance of 250–600 Ω to the connection.
16
18
20
22
Supply voltage VDC (volts)
Using ProLink III with the transmitter
Operating range
24
26
28
30
233