Transmission By The Fieldbus - WAGO -I/O-SYSTEM 750 User's Installation And Configuration

Modular i/o system ethernet tcp/ip
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

86 • Fieldbus controller 750-842
Programming the PFC with WAGO-I/O-PRO 32

3.2.7.2.2 Transmission by the fieldbus

The PC and the controller are physically connected via the Ethernet cable.
For data transmission, a suitable communication driver is required. This driver
is entered in the "Communication parameters" dialog in WAGO-I/O-PRO
32.
1. Start the WAGO-I/O-PRO 32 software by 'Start/Programs' or by double
2. In the "Online" menu click on the "Communication parameters" menu
3. Select the New button on the right hand side of the Communications Pa-
4. While the Ethernet driver is selected (click on the new driver you selected
5. Under "Online" click on the "Log-on" menu point to log into the control-
6. If no program is contained in the controller, a window appears asking
7. As soon as the program is loaded, you can start it by selecting "Online"
8. To terminate the online operation, return by the "Online" menu and click
clicking on the WAGO-I/O-PRO-32 symbol on your desk top.
point.
The "Communication parameters" dialog opens. The basic setting of this
dialog has no entries. This is assuming that you have not used the software
to configure any other couplers.
rameters dialog box. Select the "Ethernet_TCP_IP" driver (it is the last en-
try). You can enter a name in the "Name" field located in the top-left of the
dialog box. After all data has been entered click OK.
in the previous step). The following entries have to appear in the center
window of the dialog: -Port No.: 2455 and –IP address: (the IP address of
your controller assigned via BootP).
If necessary, change the entry accordingly.
You can now begin testing the controller.
Note
To be able to access the controller, the coupler has to have an IP address,
and the operating mode switch of the controller must be in the centerre or
top position.
ler.
(During online operation, the WAGO-I/O-PRO 32 server is active. The
communication parameters cannot be polled.)
whether or not the program is to be loaded.
Confirm with "Yes".
Subsequently the current program is loaded.
menu, then "Start".
At the right-hand end of the status bar, the system displays "ONLINE
RUNNING".
on the "Log-off" menu point.