Initial Steps - Danfoss PVED-CLS Startup Manual

Hide thumbs Also See for PVED-CLS:
Table of Contents

Advertisement

Application Guide
PVED-CLS startup guide
Introduction
PVED-CLS initial steps
6 |
©
Danfoss | October 2018
1. Open the Service Tool
2. Optional: If changing the firmware to a different revision, flash the Main and Safety Controller
(Release Package > Software)
See Section 6.2 (pages 23-27) of the PLUS+1
firmware revision, please look at the Firmware Release Note found in the Firmware Release Package
of the selected revision for additional steps.
Reverting to an early revision of firmware may not be possible with the Service Tool depending on
the specific revisions. Please contact the Danfoss technical representative if you have concerns about
changing firmware.
3. Install Diagnostic Data Files of selected Firmware Revision (Release Package > Diagnostic data
files).
See Section 6.1 (pages 21-22) of the PLUS+1
package under /Service tool folder.
4. Open .P1D file in the Service Tool (Release Package > Service Tool)
5. Select OEM on the info page
6. Click Edit PSAC and enter correct hexadecimal number
7. Click OK
Service Tool user guide. When changing to a newer
®