Vega VEGAPULS 62 Operating Instructions Manual page 40

4...20 ma/hart two-wire
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

Additonal settings/Sen-
sor length
Additional settings - Re-
set
VEGAPULS 62 • 4 ... 20 mA/HART two-wire
6 Set up with the indicating and adjustment module
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [ESC] and [->] key.
Caution:
If the instrument is used as part of an overfill protection system
according to WHG (Water Resources Act), please note the following:
If a linearisation curve is selected, the measuring signal is no longer
compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.
With radar sensors with standpipe antenna, the sensor length is
already preset in this menu item. When shortening the standpipe
antenna afterwards, this value must be corrected respectively.
With a reset, all settings despite a few exceptions will be reset. The
exceptions are: PIN, language, lighting, SIL and HART mode.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of
shipment from the factory incl. the order-specific settings. A created
false signal suppression, user-programmable linearization curve as
well as the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and
laboratory parameters to the default values of the respective instru-
ment. A created false signal suppression, user programmable
linearization curve as well as the measured value memory will be
deleted.
39