Operating Instructions

VEGAPULS 66
4 ... 20 mA/HART - two-wire
Document ID: 28438

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VEGAPULS 66 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vega VEGAPULS 66

  • Page 1: Operating Instructions

    Operating Instructions VEGAPULS 66 4 … 20 mA/HART - two-wire Document ID: 28438...
  • Page 2: Table Of Contents

    Set up with PACTware and other adjustment programs ............ 47 Connect the PC ......................47 Parameter adjustment with PACTware ................48 7.3 Parameter adjustment with AMS™ and PDM ..............49 Saving the parameterisation data ................... 50 8 Maintenance and fault rectification ..................51 VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 3 10.4 Trademark ........................66 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2017-09-22 VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 4: About This Document

    Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, tip, note This symbol indicates helpful additional information.
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use VEGAPULS 66 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 6: Safety Label On The Instrument

    For operation inside of closed vessels, points a to f in annex E of EN 302372 must be fulfilled. FCC and IC conformity (only for USA/Canada) VEGAPULS 66 is FCC and IC approved: • FCC ID: O6QPULS6566 VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 7: Installation And Operation In The Usa And Canada

    2 For your safety • IC: 3892A-PS6566 Modifications not expressly approved by VEGA will lead to expiry of the operating licence according to FCC. VEGAPULS 66 is in conformity with part 15 of the FCC regulations. Take note of the respective operating regulations: • This device may not cause interference, and •...
  • Page 8: Product Description

    The VEGAPULS 66 consists of the components: • Process fitting with antenna system • Housing with electronics, optionally available with plug connector, optionally available with connection cable • Housing cover, optionally available with display and adjustment module PLICSCOM The components are available in different versions. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 9: Principle Of Operation

    VEGAPULS 66 is a radar sensor in C-band (emitting frequency ap- prox. 6 GHz) for continuous level measurement. A special version of VEGAPULS 66 is available for each area of appli- cation. The version with flange and horn antenna is particularly suit- VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 10: Packaging, Transport And Storage

    Transport inspection The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con- cealed defects must be appropriately dealt with. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 11: Accessories And Replacement Parts

    You can find further information in the operating instructions "Interface adapter VEGACONNECT" (Document-ID 32628). VEGADIS 81 The VEGADIS 81 is an external display and adjustment unit for VEGA plics sensors. ® For sensors with double chamber housing the interface adapter "DISADAPT"...
  • Page 12 "Flanges according to DIN-EN-ASME-JIS" (Document-ID 31088). Electronics module "VEGAPULS series 60" is a replacement part for Electronics module radar sensors of VEGAPULS series 60. A different version is available for each type of signal output. You can find further information in the operating instructions "Elec- tronics module VEGAPULS series 60" (Document-ID 30176). VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 13: Mounting

    Prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. Measuring range The reference plane for the measuring range is the lower edge of the flange or the seal surface of the thread. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 14 The emitted radar impulses of VEGAPULS 66 are electromagnetic waves. The polarisation plane is the direction of the electrical share. Their position is marked on the instrument. Fig. 4: Position of the polarisation plane of VEGAPULS 66 Marking hole Suitability for the process...
  • Page 15: Mounting Instructions

    Mounting instructions Installation position When mounting the VEGAPULS 66, keep a distance of at least 500 mm (19.69 in) to the vessel wall. If the sensor is installed in the center of dished or round vessel tops, multiple echoes can arise.
  • Page 16 Fig. 7: Inflowing liquid Mounting socket The socket piece should be dimensioned in such a way that the an- tenna end protrudes at least 10 mm (0.4 in) out of the socket. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 17 If the socket height cannot be maintained, an antenna extension will be necessary. This prevents from false reflections of the socket piece. Fig. 9: Tube extension Tip: VEGAPULS 66 is optionally also available with antenna extension. The antenna length can thus be selected such that the antenna end protrudes 10 mm (0.4 in) out of the socket. Sensor orientation In liquids, direct the sensor as perpendicular as possible to the prod- uct surface to an achieve optimum measurement.
  • Page 18 Foam generation Through the action of filling, stirring and other processes in the vessel, dense foams which considerably damp the emitted signals may form on the product surface. If foam is causing measurement errors, the largest possible radar antenna should be used. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 19 Vent hole max. ø 5 mm (0.2 in) If possible, the diameter of the sensor antenna should correspond to the inner diameter of the tube. With VEGAPULS 66 this is approx. 50 mm (1.969 in) depending on the antenna. The sensor can be used with tube diameters between 50 …...
  • Page 20 4 Mounting 100% Fig. 14: VEGAPULS 66 in a bypass tube. The polarisation marking on the process fitting must be in one plane with the tube holes or the tube connection openings. Marking of the polarisation direction When the sensor is mounted on a bypass tube, the distance from VEGAPULS 66 to the upper tube connection should be approx.
  • Page 21: Connecting To Power Supply

    Class 2 power supply unit: limited voltage and power level, special insulation against circuits with higher voltage. SELV (Safety Extra Low Voltage) power supply unit: limited voltage level, special insulation against circuits with higher voltage VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 22: Connection Procedure

    4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires 5. Insert the cable into the sensor through the cable entry VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 23: Wiring Plan, Single Chamber Housing

    12. Screw the housing lid back on The electrical connection is finished. Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex-ia version. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 24 Fig. 18: Electronics and terminal compartment - single chamber housing Plug connector for VEGACONNECT (I²C interface) Spring-loaded terminals for connection of the external indication VEGADIS Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 25: Wiring Plan, Double Chamber Housing

    Fig. 20: Double chamber housing Housing cover - connection compartment Blind plug or plug M12 x 1 for VEGADIS 61 (optional) Housing cover - electronics compartment Filter element for air pressure compensation Cable gland VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 26 Terminal compartment I 2 C Fig. 22: Terminal compartment - double chamber housing Spring-loaded terminals for voltage supply Plug connector for VEGACONNECT (I²C interface) Ground terminal for connection of the cable screen VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 27: Wiring Plan, Double Chamber Housing Ex D

    Fig. 24: Double chamber housing Housing cover - connection compartment Blind plug or plug M12 x 1 for VEGADIS 61 (optional) Housing cover - electronics compartment Filter element for air pressure compensation Cable gland VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 28 Internal connection cable to the connection compartment Terminals for VEGADIS 81 Terminal compartment Fig. 26: Connection compartment, Ex-d-ia double chamber housing Spring-loaded terminals for power supply and cable screen Ground terminal for connection of the cable screen VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 29: Wiring Plan - Version Ip 66/Ip 68, 1 Bar

    Brown (+) and blue (-) to power supply or to the processing system Shielding Switch-on phase Switch-on phase After connecting VEGAPULS 66 to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 seconds: •...
  • Page 30: Set Up With The Display And Adjustment Module Plicscom

    4. Screw housing lid with inspection window tightly back on Disassembly is carried out in reverse order. The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 31: Adjustment System

    Adjustment system Fig. 30: Display and adjustment elements LC display Indication of the menu item number Adjustment keys • [OK] key: Key functions VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 32: Setup Steps

    The radar sensor measures the distance from the sensor to the Parameterization example product surface. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 33 Min. adjustment 0.00 % 5.000 m(d) 4.000 m(d) 3. Prepare the % value for editing with [OK] and set the cursor to the requested position with [->]. Set the requested percentage value VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 34 With solids, you can also choose between "Powder/Dust", "Granular/ Pellets" or "Ballast/Pebbels". Through this additional selection, the sensor is adapted perfectly to the product and measurement reliability, particularly in products with poor reflective properties, is considerably increased. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 35 Enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [->] key. Caution: Note the following if the VEGAPULS 66 with corresponding approval is used as part of an overfill protection system according to WHG (Water Resources Act): VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 36 "Display" and the adjustment unit in the menu "Device settings": • Indication value "Distance": Presentation of the measured value in the selected adjustment unit, e.g. m(d). Displayed value ▼ Scaled VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 37 "Trend curve". Then the values can be displayed on a time axis. The oldest measured values are always deleted. In the menu item "Choose curve", the respective curve is selected. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 38 A false echo memory should be created with low level so that all potential interfering reflec- tions can be detected. False signal suppression Change now? Proceed as follows: 1. Move from the measured value display to the main menu by pushing [OK]. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 39 Service - Extended set- The menu item "Extended setting" offers the possibility to optimise ting VEGAPULS 66 for applications in which the level changes very quickly. To do this, select the function "Quick level change > 1 m/min.". Extended setting quick level change > 1 m/min.
  • Page 40 If the "Reset" is carried out, the sensor resets the values of the follow- ing menu items to the reset values (see table): Menu item Reset value Max. adjustment 0 m(d) Min. adjustment Meas. range end in m(d) Sensor-specific basic adjustment. Depending on the sensor type, see chapter "Technical data". VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 41 The following languages are available, e.g. in software version 3.50: • Deutsch • English • Français • Espanõl • Pycckuu Special parameters are parameters which are set customer-specifically on the service level with the adjustment software PACTware. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 42 The following data are read out or written with this function: • Measured value presentation • Adjustment • Medium The 4 … 20 mA signal of the sensor is switched off. The sensor uses a constant current of 4 mA. The measuring signal is transmitted exclusively as a digital HART signal. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 43 • Instrument type • Serial number: 8-digit number, e.g. 12345678 Instrument type Serial number • Date of manufacture: Date of the factory calibration • Software version: Edition of the sensor software VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 44: Menu Schematic

    Max. adjustment Medium Vessel form ▼ 0.00 % 100.00 % Liquid ▼ ▼ not known not known 30.000 m(d) 0.000 m(d) 0.665 m(d) 0.665 m(d) Damping Linearisation curve Sensor-TAG ▼ Sensor linear VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 45 4 mA ▼ max. current: 20 mA Reset Unit of measurement Language ▼ ▼ ▼ Select reset? m(d) Deutsch Not activated HART mode Copy sensor data Standard Copy sensor data? Enable? Address 0 VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 46: Saving The Parameterisation Data

    They are thus available for multiple use or service purposes. If VEGAPULS 66 is equipped with a display and adjustment module, the most important data can be read out of the sensor into the display and adjustment module.
  • Page 47: Set Up With Pactware And Other Adjustment Programs

    Fig. 33: Connection via VEGACONNECT externally I²C bus (com.) interface on the sensor I²C connection cable of VEGACONNECT VEGACONNECT USB cable to the PC Necessary components: • VEGAPULS 66 • PC with PACTware and suitable VEGA DTM VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 48: Parameter Adjustment With Pactware

    Power supply unit or processing system Note: With power supply units with integrated HART resistance (internal resistance approx. 250 Ω), an additional external resistance is not necessary. This applies, e. g. to the VEGA instruments VEGATRENN 149A, VEGADIS 371, VEGAMET 381. Common Ex separators are also usually equipped with a sufficient current limitation resistance. In such cases, VEGACONNECT 4 can be connected parallel to the 4 …...
  • Page 49: Parameter Adjustment With Ams™ And Pdm

    Parameter adjustment with AMS™ and PDM For VEGA sensors, instrument descriptions for the adjustment programs AMS™ and PDM are available as DD or EDD. The instru- ment descriptions are already implemented in the current versions of AMS™ and PDM. For older versions of AMS™ and PDM, a free-of-charge download is available via Internet. Move to www.vega.com. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 50: Saving The Parameterisation Data

    It is recommended to document or save the parameter adjustment data. That way they are available for multiple use or service purposes. The VEGA DTM Collection and PACTware in the licensed, profession- al version provide suitable tools for systematic project documentation and storage. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 51: Maintenance And Fault Rectification

    24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is manned 7 days a week round-the-clock. Since we offer this service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.
  • Page 52: Exchanging The Electronics Module

    Software update The following components are required to update the instrument software: • Instrument • Voltage supply • Interface adapter VEGACONNECT • PC with PACTware • Current instrument software as file VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 53: How To Proceed If A Repair Is Necessary

    Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 54: Dismount

    WEEE directive. Correct disposal avoids negative effects on humans and the environ- ment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 55: Supplement

    20.5 mA, 22 mA, < 3.6 mA (adjust- able) Max. output current 22 mA Load see load diagram under Power supply Damping (63 % of the input variable) 0 … 999 s, adjustable Met NAMUR recommendation NE 43 VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 56 Corresponds to the range with 50 % of the emitted power Time to output the correct level (with max. 10 % deviation) after a sudden level change. At the aperture of a horn antenna with ø 150 mm VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 57: Ambient Conditions

    180 °C/356 °F 2.1 % steam) Ambient conditions Ambient, storage and transport tempera- -40 … +80 °C (-40 … +176 °F) ture Process conditions For the process temperature and the vessel pressure, you also have to note the specifications on the type label! Always the lowest value is applicable! Incl. non-linearity, hysteresis and non-repeatability. Relating to the nominal measuring range, in the temperature range -40 … +80 °C . VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 58 FKM, FFKM (Kalrez 6375) Ʋ for tube diameter 10 mm Ʋ Opening pressure 0.5 bar (7.252 psi) Ʋ Nominal pressure stage PN 250 Tested according to the guidelines of German Lloyd, GL directive 2. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 59 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - standard PE Black Ʋ Colour - standard PUR Blue Ʋ Colour - Ex-version Blue Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF. VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 60 Ʋ Reference voltage 500 V AC Electrical protective measures Protection rating Housing material Version IP-protection class NEMA protection Plastic Single chamber IP 66/IP 67 Type 4X Double chamber IP 66/IP 67 Type 4X VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 61 Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com "Instrument search (serial number)" as well as in the general download area.
  • Page 62: Dimensions

    Plastic single chamber (IP 66/IP 67) Aluminium - single chamber Aluminium - double chamber Stainless steel single chamber (electropolished) Stainless steel single chamber (precision casting) Stainless steel double chamber housing (precision casting) VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 63 DN 250 PN 16 14.96" 2" 150 lb 3" 150 lb 2.68" 4" 150 lb 4.45" 6" 150 lb 8.07" 11.65" 8" 150 lb 10" 150 lb 14.96" Fig. 39: VEGAPULS 66, standard version VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 64 10" 150 lb 14.96" Fig. 40: VEGAPULS 66, standard version with rinsing air connection Rinsing air connection G¼ A for mounting of a suitable adapter Reflux valve - enclosed unassembled (with non-Ex optionally available, with Ex in the scope of delivery), for tube diameters 10 mm VEGAPULS 66 •...
  • Page 65 10 Supplement VEGAPULS 66, high temperature versions Fig. 41: VEGAPULS 66, high temperature version For process temperatures up to 250 °C (482 °F) For process temperatures up to 400 °C (752 °F) VEGAPULS 66 • 4 … 20 mA/HART - two-wire...
  • Page 66: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.
  • Page 67 Notes VEGAPULS 66 • 4 … 20 mA/HART - two-wire...