4...20 ma/hart two-wire
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

VEGAPULS 62 • 4 ... 20 mA/HART two-wire
5
Insert the cable into the sensor through the cable entry
Fig. 18: Connection steps 5 and 6
6
Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with cable end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, press the terminal head with a small screwdriver;
the terminal opening is freed. When the screwdriver is released, the
terminal closes again.
7
Check the hold of the wires in the terminals by lightly pulling on
them
8
Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
9
Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10 Screw the housing cover on
The electrical connection is finished.
Information:
The terminal block is pluggable and can be removed from the
electronics. For this purpose, lift the terminal block with a small
screwdriver and pull it out. When inserting the terminal block again,
you should hear it snap in.