This symbol indicates special instructions for Ex applications. List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. VEGAPULS 62 • 4 ... 20 mA/HART...
During work on and with the device the required personal protection equipment must always be worn. 2.2 Appropriate use VEGAPULS 62 is a sensor for continuous level measurement. You can find detailed information on the application range in chapter "Product description".
NAMUR recommendation NE 53 in respect to compat- ibility. VEGA instruments are generally upward and downward compatible: Sensor software to DTM VEGAPULS 62 HART, PA or FF DTM VEGAPULS 62 for adjustment software PACTware™ Indicating and adjustment module for sensor software The parameter adjustment of the basic sensor functions is independent of the software version.
Modifications not expressly approved by VEGA will lead to expiry of the operating licence according to FCC/IC. VEGAPULS 62 is in conformity with part 15 of the FCC directives and fulfills the RSS-210 regulations. Note the corresponding regulations for operation:...
2.12 Functional range of approved instruments Instruments with specific approvals are partly supplied with an earlier hardware or software version. For approval-technical reasons, some functions for these instruments will be available only at a later date. VEGAPULS 62 • 4 ... 20 mA/HART...
The environment man- agement system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environ- mental instructions in this manual: Chapter "Packaging, transport and storage" Chapter "Disposal" VEGAPULS 62 • 4 ... 20 mA/HART...
Product description 3 Product description 3.1 Configuration The VEGAPULS 62 radar sensor is available in two electronics Versions versions: Standard electronics type PS60KH Electronics with increased sensitivity type PS60KD The respective version can be determined by means of the type label on the electronics.
VEGAPULS 62 is a radar sensor in K-band (emitting frequency Area of application approx. 26 GHz) for continuous level measurement. A suitable version of VEGAPULS 62 is available for each area of application: The version with "thread and horn antenna with ø 40 mm (1.575 in)"...
"Heating for indicating and adjustment module". This function is generally not available for approved instruments. 3.3 Operation VEGAPULS 62 can be adjusted with different adjustment media: with indicating and adjustment module with the suitable VEGA DTM in conjunction with an adjustment software according to the FDT/DTM standard, e.g.
Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see "Supplement - Storage and transport temperature Technical data - Ambient conditions" Relative humidity 20 … 85 % VEGAPULS 62 • 4 ... 20 mA/HART...
Use the recommended cables (see chapter "Connecting to Moisture power supply") and tighten the cable gland. You can give your VEGAPULS 62 additional protection against moisture penetration by leading the connection cable down- ward in front of the cable entry. Rain and condensation water can thus drain off.
Information: If the medium reaches the antenna, buildup can form on it and cause faulty measurements later on. Make sure that the wetted parts of VEGAPULS 62, especially Wetted materials the seal and process fitting, are suitable for the existing process conditions such as pressure, temperature etc.
4 Retighten the antenna with hexagon screws to the antenna socket; torque max. 10 Nm (7.5 lbf ft) Note: VEGAPULS 62 with rinsing air connection or antenna extension is provided with a notch on the antenna socket. This notch must correspond to the marking on the hexagon of the process fitting (the marking specifies the position of the...
Page 18
flange). The antenna must therefore be disconnected from the flange before mounting. Proceed as follows: 1 Clamp VEGAPULS 62 with the flange, e.g. in a bench vice 2 Hold the connection piece (3) with a wrench SW 22 on the flattenings...
VEGAPULS 62 with parabolic antenna. When mounting VEGAPULS 62, keep a distance of at least Installation position 200 mm (7.874 in) to the vessel wall. If the sensor is installed in the center of dished or round vessel tops, multiple echoes can arise.
Page 20
Fig. 7: Vessel with conical bottom Do not mount the instruments in or above the filling stream. Inflowing medium Make sure that you detect the product surface, not the inflowing product. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 21
Fig. 9: Recommended socket mounting If the reflective properties of the medium are good, you can mount VEGAPULS 62 on sockets which are higher than the length of the antenna. You will find recommended values for socket heights in the following illustration. The socket end should be smooth and burr-free, if possible also rounded.
Page 22
150 mm/6" 800 mm Fig. 10: Deviating socket dimensions Tip: VEGAPULS 62 is optionally also available with antenna extension. Hence the antenna length can be selected such that the antenna end protrudes 10 mm (0.4 in) out of the socket.
Page 23
If foams lead to measurement errors, you should use the biggest possible radar antennas and low frequency radar sensors e.g. VEGAPULS 65, 66 (C-band). VEGAPULS 62 • 4 ... 20 mA/HART...
Page 24
With VEGAPULS 62 this is approx. 40 mm (1.575 in). The sensor can be used with tube diameters between 40 … 80 mm (1.575 … 3.15 in). VEGAPULS 62 • 4 ... 20 mA/HART...
Page 25
(see illustration: "VEGAPULS in a bypass tube"). 100% Fig. 15: VEGAPULS 62 in a bypass tube. The polarisation marking on the process fitting must be in one plane with the tube holes or the tube connection openings.
Page 26
Installation of the sensor at the inlet side Installation in the center of the flume and vertical to the liquid surface Distance to the Venturi flume Min. distance of the sensor to max. storage level VEGAPULS 62 • 4 ... 20 mA/HART...
Page 27
The illustration shows an example for a gauge measurement. Gauge measurement In general, the following points must be observed: Installation of the sensor in a protected area Installation vertical to the liquid surface VEGAPULS 62 • 4 ... 20 mA/HART...
Influence of additional instruments in the circuit (see load values in chapter "Technical data") VEGAPULS 62 is connected with standard two-wire cable Selecting connection without screen. An outer cable diameter of 5 … 9 mm ensures cable the seal effect of the cable entry.
Connecting to power supply On VEGAPULS 62 with cable gland ½ NPT and plastic Cable gland ½ NPT housing, a metal ½" threaded insert is moulded in the plastic housing. Caution: No grease should be used when screwing the NPT cable gland or steel tube into the threaded insert.
12 Screw the housing cover on The electrical connection is finished. 5.3 Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex-ia version. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 32
Spring-loaded terminals for connection of the external indication VEGADIS Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply Wiring plan Display I 2 C Fig. 22: Wiring plan, single chamber housing Voltage supply/Signal output VEGAPULS 62 • 4 ... 20 mA/HART...
Display I 2 C 5 6 7 8 Fig. 24: Electronics compartment, double chamber housing Plug connector for VEGACONNECT (I²C interface) Internal connection cable to the connection compartment Terminals for VEGADIS 61 VEGAPULS 62 • 4 ... 20 mA/HART...
Page 34
Plug connector for VEGACONNECT (I²C interface) Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply Wiring plan I 2 C Fig. 26: Wiring plan, double chamber housing Voltage supply/Signal output VEGAPULS 62 • 4 ... 20 mA/HART...
(+) and blue (-) to power supply or to the processing system Shielding 5.7 Switch on phase After connecting VEGAPULS 62 to power supply or after a Switch on phase voltage recurrence, the instrument carries out a self-check for approx.
4 Screw housing cover with inspection window tightly back Removal is carried out in reverse order. The indicating and adjustment module is powered by the sensor, an additional connection is not necessary. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 39
Set up with the indicating and adjustment module PLICSCOM Fig. 32: Installation of the indicating and adjustment module Note: If you intend to retrofit VEGAPULS 62 with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. VEGAPULS 62 • 4 ... 20 mA/HART...
PACTware™ or DTM. HART mode Standard Address 0 As VEGAPULS 62 is a distance measuring instrument, the Parameter adjustment distance from the sensor to the product surface is measured. To have the real product level displayed, an allocation of the measured distance to the percentage height must be made.
Page 42
Keep in mind that the max. level must lie below the dead band. 3 Save the settings with [OK] and move to "Medium selection" with [->]. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 43
Vessel form Storage tank Information: With VEGAPULS 62 with electronics version "Increased safety", "Solid" is preset as factory setting. However, the instrument should be used preferably in liquids. In such cases, the vessel form should be set to "Storage tank" during setup.
Page 44
[->] key. Caution: Note the following, if VEGAPULS 62 is used as part of an overfill protection system according to WHG: If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level.
Page 45
The filling level would then no longer be detectable in this area. The menu item "Extended setting" offers the possibility to Extended setting/Quick optimise VEGAPULS 62 for applications with quick level level change changes. For this purpose select the function "Quick level change >1 m/min.".
Page 46
4 mA Current output - failure <3.6 mA Unit of measurement m(d) The values of the following menu items are not reset to the reset values (see chart) with "Reset": Sensor-specific basic adjustment. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 47
You will find a detailed description of these menu items in the operating instructions manual "Indicating and adjustment module". Special parameters are parameters which are set customer-specifically on the service level with the adjustment software PACTware™. VEGAPULS 62 • 4 ... 20 mA/HART...
Diagnostics Service Info Displayed value Display unit Scaling Lighting 0 % = 0.0 m³ Scaled Volume Switched off ▼ 100 % = 100 m³ m³ Diagnostics Basic adjustment Display ▶ Diagnostics Service Info VEGAPULS 62 • 4 ... 20 mA/HART...
Page 49
Info Basic adjustment Display Diagnostics Service ▶ Info Sensor type Date of manufacture Last change using PC Sensor characteristics 4. July 2007 Software version Display now? Serial number 3.50 4. July 2007 12345678 VEGAPULS 62 • 4 ... 20 mA/HART...
They are hence available for multiple use or service purposes. If VEGAPULS 62 is equipped with an indicating and adjust- ment module, the most important data can be read out of the sensor into indicating and adjustment module. The procedure is described in the operating instructions manual "Indicating...
With power supply units with integrated HART resistance (internal resistance approx. 250 Ω), an additional external resistance is not necessary. This applies, e. g. to the VEGA instruments VEGATRENN 149A, VEGADIS 371, VEGAMET 381). Also usual Ex separators are most of the time equipped with a sufficient current limitation resistor.
All currently available VEGA DTMs are provided in the DTM Collection on CD and can be obtained from the responsible VEGA agency for a token fee. This CD includes also the up-to- date PACTware™ version. The basic version of this DTM Collection incl.
Maintenance and fault rectification 8 Maintenance and fault rectification 8.1 Maintenance When used as directed in normal operation, VEGAPULS 62 is completely maintenance free. 8.2 Remove interferences VEGAPULS 62 offers maximum reliability. Nevertheless, faults Causes of malfunction can occur during operation. These may be caused by the following, e.g.:...
Page 55
à Exchange instrument or return instrument for repair Depending on the failure reason and measures taken, the Reaction after fault rec- steps described in chapter "Set up" must be carried out again, tification if necessary. VEGAPULS 62 • 4 ... 20 mA/HART...
PS-E.60KHD (D = approvals KX, KF according to VEGA product list) PS-E.60KHE (E = approvals CX, DX, CK, CI, DM, XM, CM, DI, EX, GI, GX, UX, UF according to VEGA product list) Oscillator PS-E.60KD is suitable for K band VEGAPULS 61, 4 … 20 mA/HART with 62, 63 - 4 …...
PS-E.60KDD (D = approvals KX, KF according to VEGA product list) PS-E.60KDE (E = approvals CX, DX, CK, CI, DM, XM, CM, DI, EX, GI, GX, UX, UF according to VEGA product list) 8.4 Instrument repair If a repair is necessary, please proceed as follows: You can download a return form (23 KB) from our Internet homepage www.vega.com under: "Downloads - Forms and...
Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return. VEGAPULS 62 • 4 ... 20 mA/HART...
5 … 16.2 kg (11 … 35.7 lbs), depending on - Process fitting - flange the flange size and housing Output variable Output signal 4 … 20 mA/HART Signal resolution 1.6 µA VEGAPULS 62 • 4 ... 20 mA/HART...
Page 60
Interval Beam angle 3 dB with horn antenna, depending on antenna diameter - ø 40 mm (1.575 in) 22° - ø 48 mm (1.89 in) 18° - ø 75 mm (2.953 in) 10° VEGAPULS 62 • 4 ... 20 mA/HART...
Page 61
30 m -3 mm -10 mm Fig. 36: Deviation VEGAPULS 62 with horn antenna in mm, measuring range in m Time to output the correct level (with max. 10 % deviation) after a sudden level change. Incl. non-linearity, hysteresis and non-repeatability.
Page 62
30 mm 15 mm 1,0 m 30 m -15 mm -30 mm Fig. 38: Deviation VEGAPULS 62 with horn antenna and increased sensitivity in mm, measuring range in m 0.180 in 0.590 in 3.280 ft 98.43 ft - 0.590 in - 0.180 in...
Page 63
Fig. 41: Deviation VEGAPULS 62 with parabolic antenna in Inch, measuring range in ft 40 mm 15 mm -15 mm 2,0 m 30 m -40 mm Fig. 42: Deviation VEGAPULS 62 with parabolic antenna and increased sensitivity in mm, measuring range in m VEGAPULS 62 • 4 ... 20 mA/HART...
Page 64
6.562 ft 98.43 ft - 1.574 in Fig. 43: Deviation VEGAPULS 62 with parabolic antenna and increased sensitivity in Inch, measuring range in ft Influence of the ambient temperature to the sensor electronics Average temperature coefficient of 0.03 %/10 K the zero signal (temperature error) Influence of the superimposed gas and pressure to the accuracy...
Page 65
4 g and 5 … 100 Hz Data on rinsing air connection max. 6 bar (87.02 psi) Pressure Air quantity see diagram Tested according to the regulations of German Lloyd, GL directive 2. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 66
Reflux valve - attached (with non-Ex option, with Ex in the scope of delivery) 316Ti - Material - Seal FKM (Viton), Kalrez - for tube diameter 6 mm - opening pressure 0.5 bar (7.25 psi) - Nominal pressure stage PN 250 VEGAPULS 62 • 4 ... 20 mA/HART...
Page 67
1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper M20 x 1.5; 1 x blind stopper M16 x 1.5 Depending on the version M12 x 1, according to DIN 43650, Harting, Am- phenol-Tuchel, 7/8" FF. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 68
Supply voltage with lighted indicating and adjustment module - Non-Ex instrument 20 … 36 V DC - EEx-ia instrument 20 … 30 V DC - EExd ia instrument 20 … 36 V DC VEGAPULS 62 • 4 ... 20 mA/HART...
Page 69
20 … 30 V DC - EExd ia instrument 20 … 36 V DC Permissible residual ripple - <100 Hz <1 V - 100 Hz … 10 kHz <10 mV see diagram Load VEGAPULS 62 • 4 ... 20 mA/HART...
Page 70
1G, 1/2G, 2G EEx ia IIC T5+ATEX II 1/2D IP6X T6 A suitable cable is the prerequisite for maintaining the protection class. Available or applied for, depending on the order specification. Deviating data with Ex applications: see separate safety instructions. VEGAPULS 62 • 4 ... 20 mA/HART...
Page 71
I-III, Div 1 (IS); FM Cl.I-III, Div 1(IS)+Cl.I-III, Div 1 Gr.C-G (XP) CSA CI.I, Div2 (NI)+CI.II, III, Div1 (DIP); CSA CI.I-III, Div 1 (IS); CSA Cl.I-III, Div 1(IS)+Cl.I- III, Div 1 Gr.C-G (XP) Ship approvals GL, LRS, ABS, CCS, RINA Others VEGAPULS 62 • 4 ... 20 mA/HART...
M20x1,5/ ½ NPT Fig. 48: Housing versions in protection IP 66/IP 68, 1 bar (with integrated PLICSCOM the housing is 9 mm/0.35 in higher) Stainless steel housing Aluminium double chamber housing Aluminium housing VEGAPULS 62 • 4 ... 20 mA/HART...
Page 73
4" ø95 inch " ø1 " 1½" " ø1 " 2" " ø2 " 3" " ø3 " 4" Fig. 49: VEGAPULS 62 - horn antenna in threaded version Standard with temperature adapter VEGAPULS 62 • 4 ... 20 mA/HART...
Page 74
4" " ø3 " Fig. 50: VEGAPULS 62 - horn antenna in threaded version with purging air connection Standard with temperature adapter Purging air connection G⅛ A for mounting of a suitable adapter Reflux valve - attached (with non-Ex optionally available, with Ex in the scope of delivery), for tube diameters 6 mm VEGAPULS 62 •...
Page 75
" ø3 " 4" Fig. 51: VEGAPULS 62 - horn antenna in threaded version with purging air connection and antenna extension Standard with temperature adapter An antenna extension causes a reduction of sensitivity at close range in dependence on product properties. A suitable support for the antenna extension must be provided as required by its length.
Page 76
" " 6" 150 lb 279,4 25,4 241,3 8xø22,4 6" 150 lb 11" 1" " 8xø " " " Fig. 52: VEGAPULS 62 - horn antenna in flange version Standard with temperature adapter VEGAPULS 62 • 4 ... 20 mA/HART...
Page 77
" 8xø " " Fig. 53: VEGAPULS 62 - horn antenna in flange version with purging air connection Standard with temperature adapter Purging air connection G⅛ A for mounting of a suitable adapter Reflux valve - attached (with non-Ex optionally available, with Ex in the scope of delivery), for tube diameters 6 mm VEGAPULS 62 •...
Page 78
Supplement VEGAPULS 62 - parabolic antenna in threaded version 46mm ") G1½A / 1½ NPT ø 244mm (9 ") Fig. 54: VEGAPULS 62 - parabolic antenna in threaded version Standard with temperature adapter VEGAPULS 62 • 4 ... 20 mA/HART...
Page 79
" " 8xø " 11" 1" " 8xø " 6" 150 lb 279,4 25,4 241,3 8xø22,4 6" 150 lb Fig. 55: VEGAPULS 62 - parabolic antenna in flange version Standard with temperature adapter VEGAPULS 62 • 4 ... 20 mA/HART...
Page 80
11,5 182,5 4xø22 DN 100 / 4" Fig. 56: VEGAPULS 62 - parabolic antenna and swivelling holder with purging air connection Standard with temperature adapter Purging air connection G⅛ A for mounting of a suitable adapter Reflux valve - attached (with non-Ex optionally available, with Ex in the scope of delivery), for tube diameters 6 mm VEGAPULS 62 •...
Page 81
Supplement 10.3 Industrial property rights VEGA product lines are global protected by industrial property rights. Further information see http://www.vega.com Only in U.S.A.: Further information see patent label at the sensor housing. VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte. Nähere Informationen unter http://www.vega.com...