VEGAPULS 62 • 4 ... 20 mA/HART two-wire
4
100 %
5
0 %
Fig. 14: Configuration bypass
Radar sensor
1
2
Marking of the polarisation plane
Instrument flange
3
Distance sensor reference plane to upper tube connection
4
5
Distance of the tube connections
Ball valve with complete opening
6
Instructions for orientation:
Note marking of the polarisation plane on the sensor
l
With threaded fitting, the marking is on the hexagon, with flange
l
connection between the two flange holes
The marking must show to the direction of the tube connections to
l
the vessel
Instructions for the measurement:
The 100 % point must not be above the upper tube connection to
l
the vessel
The 0 % point must not be below the lower tube connection to the
l
vessel
Min. distance sensor reference plane to the upper edge upper
l
tube connection > 300 mm
For the parameter adjustment, select "Application standpipe" and
l
enter the tube diameter to compensate errors due to running time
shift
A false signal suppression with integrated sensor is recommended
l
but not mandatory
The measurement through a ball valve with complete run is
l
possible
Constructional requirements on the bypass pipe:
4 Mounting
1
2
3
6
21