6 Set up with the indicating and adjustment module
Further settings/Linear-
ization curve
38
2
Confirm again with [OK].
3
Confirm again with [OK] and select with [->] "Create new".
4
Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5
All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.
A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindrical
or spherical tank - and the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed for
these vessels. They represent the correlation between the level
percentage and vessel volume. By activating the appropriate curve,
the volume percentage of the vessel is displayed correctly. If the
volume should not be displayed in percent but e.g. in l or kg, a scaling
can be also set in the menu item "Display".
VEGAPULS 62 • 4 ... 20 mA/HART two-wire