42.Bin1' / '43.Bin2' Function Binary Input - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

9.4.2.13

'42.BIN1' / '43.BIN2' Function binary input

Setting option
Purpose:
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
• Binary input 1
Normally open
OFF
on
bloc1
bloc2
uP
doWn
StoP
PST
• Binary input 2
Normally open
OFF
on
uP
doWn
StoP
PST
These parameters determine the function of the binary inputs. The
possible functions are described below. The direction of action can
be adapted to a normally closed or normally open mode.
• BIN1 or BIN2 = On or -On
Binary messages from peripherals, e.g. from pressure or
temperature switches, are read over the communication
interface or fed through a logical OR combination with other
messages to trigger the error message output.
• BIN1 = bLoc1
Use this parameter value to interlock the "Configuration" mode
against adjustment. The lock is performed e.g. with a jumper
between terminals 9 and 10.
• BIN1 = bLoc2
If binary input 1 has been activated, the "Manual" as well as
"Configuration" modes are blocked.
• BIN1 or BIN2 =
contact uP or doWn closes, or
contact -uP or -doWn opens
If the binary input is activated, the actuator uses the value
defined by the "'35.YA' Start of manipulated variable limit /
'36.YE' End of manipulated variable limit (Page 163)"
parameter for controlling in "Automatic" mode.
Parameter assignment
9.4 Description of parameters
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST
167

Advertisement

Table of Contents
loading

Table of Contents