Ahu Sensor Connection - LG PRCKD42E Owner's Manual

Ahu control kit
Table of Contents

Advertisement

AHU SENSOR CONNECTION

30
AHU SENSOR CONNECTION
Sensor / load connection
- Temperature/humidity sensor (required)
Item
Temperature/humidity
sensor
Ex: SA (Supply) Temperature/Humidity Sensor Connection
Terminal Block#1
B5
!
CAUTION
• Improper wiring of the sensor can damage the Main Controller of the AHU. Make sure to
check for any incorrect wiring before turning the power on.
1. For more information on the installation of temperature/humidity sensors, refer to the
Manual that came with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
3. Using a temperature/humidity sensor outside the temperature range different from the
above specifications can cause the unit to malfunction. However, the temperature range
can be adjusted in HMI Settings.
Specification
- Power: AC 24 V
- Output signal: DC 0~10 V
- Temperature range: -40 °C~70 °C
- Humidity range: 0~95 % RH
B6
B7
B8
G
-AHU Controller
<Included in the Control Kit>
AC 24 V(G)
Ground(G0)
DC 0~10 V(Humidity,U1)
DC 0~10 V(Temperature,U1)
Remark
Required