3. Cooling (Heating) Supply Temperature/Humidity Settings
① Temperature Settings
① Temperature Settings
The default cooling/heating temperature is 18.0 °C/30.0 °C, and it can be adjusted at an in-
crement/decrement of 0.1°C between 12.0 °C/50.0 °C and 50.0 °C
Temperature (humidity) cannot be set in the following cases.
- When the AHU ventilation temperature/humidity sensors are not installed in Administrator
Settings 2.
A warning message will appear if the temperature is outside the range, in which case you
need to re-enter the value.
② Set the Control Range
The default control range temperature is 1 °C, and it can be adjusted at an increment/decre-
ment of 1 °C between 1 °C and 2 °C.
The Control Temperature Setting range can be used only when Supply is the Control Tem-
perature standard.
An alarm message will be displayed if the control range is outside the range, in which case
you can re-enter the input value.
③ Humidity Settings
The default cooling/heating humidity is 50%, and it can be adjusted at an increment/decre-
ment of 1%RH between the range of 30~80%RH.
Humidity (ventilation) cannot be set in the following cases.
- If the ventilation/humidity sensor is not set.
A warning message will appear if the humidity is outside the range, in which case you
need to re-enter the value.
② Set the Control Range
③ Humidity Settings