LG PRCKD42E Owner's Manual page 118

Ahu control kit
Table of Contents

Advertisement

LCD SCREEN
118
Classification
① R.A. Temp.
② S.A. Temp.
③ O.A. Temp.
④ M.A. Temp.
Classification
① Control Mode
② Remote Mode
③ Address
④ Buadrate
Classification
① Version
Displays the AHU Ventilation Temperature Sensor value.
Displays the AHU Supply Temperature Sensor value.
Displays the AHU Outdoor Unit Temperature Sensor value.
Displays the AHU Mixer Temperature Sensor value.
The AHU Control Mode can be set to Local or Remote.
Settings can be configured when the Control Mode is set to 'Re-
mote', at which time you can select between Contact and Modbus.
Sets the address for communication with the remote control device
when setting the Modbus in the Remote Mode. The address can be
set between 1~247.
Displays the communication speed between the Remote Control
Device and AHU Main Control when the Remote Control Device and
Modbus are linked through a communication channel.
The communication speed is fixed at 9 600.
Displays the program version of the Main Control of the current
AHU.
The version information are subject to change at any time for prod-
uct quality/performance improvement.
Description
Description
Description