120
Coil Register
Register
1
Discrete Register
Register
10001
Ventilation Fan Operation Status
10002
10003
10004
10005
10006
10007
10008
10009
Ventilation Fan 1 Operation Status
10010
Ventilation Fan 2 Operation Status
10011
Ventilation Fan 3 Operation Status
10012
Ventilation Fan 4 Operation Status
10013
Ventilation Fan 5 Operation Status
10014
Ventilation Fan 6 Operation Status
10015
10016
10017
Supply Fan 1 Operation Status
10018
Supply Fan 2 Operation Status
10019
Supply Fan 3 Operation Status
10020
Supply Fan 4 Operation Status
10021
Supply Fan 5 Operation Status
10022
Supply Fan 6 Operation Status
10023
10024
10025
Outdoor Unit 1 Operation Status
10026
Outdoor Unit 2 Operation Status
10027
Outdoor Unit 3 Operation Status
10028
Outdoor Unit 4 Operation Status
10029
Outdoor Unit 5 Operation Status
10030
Outdoor Unit 6 Operation Status
Content
Start
Content
Supply Fan Operation Status
Smoke Detection
Replace Filter
Alarm Level 1
Alarm Level 2
Alarm Level 3
Reserved
Reserved
Reserved
Reserved
Reserved
Remarks
0: Stop / 1: Operation
Remarks
0: Stop, 1: Start
0: Stop, 1: Start
0: Not Detected, 1: Detected
0: Normal, 1: Replace
0: Normal, 1: Alarm
0: Normal, 1: Alarm
0: Normal, 1: Alarm
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start
0: Stop, 1: Start