- Set the Static Pressure Cycle
The default static pressure control cycle is set to 5 minutes, and the cycle can be set within
the range of 3~60 minutes.
- The default static pressure value is 450 Pa, and it can be adjusted at an increment/decrement
of 10 Pa between the range of 0~1,000 Pa.
※A warning message will appear if a value outside the temperature range is entered, in which
case you can re-enter the value within the range.
4. Set the Wind Speed
The fan operation frequency is determined by the wind speed (high/medium/low) configured in
Administrator Settings 1.
The frequency for each wind speed is set in the following order.
① Enter the desired input value by using the
key button.
② Enter the value and then click the 'OK'
button to enter the input value.
① Click the item to select to open a screen
where the setting can be set/entered.
② Enter the desired input value by using the
key button.
③ Enter the value and then click the 'OK'
button to enter the input value.
HMI SETTING